46 01-6203-01R3, CG Drives & Automation
4.4. Keypad parameter list
For commissioning or diagnostics using the keypad, all parameters of the inverter that can
also be accessed by means of the keypad are listed in the following "Keypad parameter
list".
• The keypad parameter list is sorted in ascending order in compliance with the "display
code" (Pxxx).
• In order to provide for quick access, all parameters of the inverter are divided into
different groups according to their function.
• Group 0 contains the configurable "Favorites". In the default setting these are the
most common parameters for the solution of typical applications. Favorites 401
• Based on the hundreds digit of the display code (Pxxx) you can quickly see in which
group the parameter is to be found on the keypad:
P1xx Group 1 Diagnostics Diagnostic/display parameters for displaying device-internal process factors,
current actual values, and status messages.
Setting of the mains voltage, selection of the control and setpoint source,
starting and stopping performance, frequency limits and ramp times.
Basic setting
116
Configuration of the motor and motor control
Motor control
134
Function assignment and configuration of the inputs and outputs
Flexible I/O configuration
487
Configuration of the network (if available)
Configuring the network
197
Group 6 Process controller
Configuration of the process controller
Configuring the process controller
350
Group 7 Additional functions
Parameterisable additional functions
Additional functions
359
The "sequencer" function serves to define a programmed sequence of speed
setpoints, PID setpoints or torque setpoints for the motor control. Switching to
the next setpoint can be executed in a time-based or event-based manner.
Sequencer
456
A complete overview of all parameter indexes can be found in the annex in the
Parameter attribute list
.
623