404 01-6203-01R3, CG Drives & Automation
No trigger assigned (trigger is constantly FALSE).
(from version 02.00)
TRUE if a change-over to network setpoint is requested via bit 6 of the
AC drive control word0x400B:001 (P592.01). Otherwise FALSE.
Notes:
Set this selection if the network setpoint is to be activated via bit 6 of
the AC drive control word.
The AC drive control word can be used with any communication
pro
tocol.
AC Drive Profile
188
12.3.5. Setpoint source of preset setpoints
The four functions "Activate preset (bit 0)" ... " Activate preset (bit 3)" enable change-over
of the setpoint to a parameterisable setpoint (preset value).
Preconditions
A setpoint change-over to the respective preset is only effected if no setpoint source with
a higher priority has been selected.
Priority of the setpoint sources
380
Details
A preset is selected in a binary-coded fashion via the triggers assigned to the four
functions "Activate preset (bit 0)" ... " Activate preset (bit 3)" in compliance with the
following truth table:
0x2631:021
0x2631:020
0x2631:019
0x2631:018
Notes:
• The frequency setpoint preset 5 is also used for the "Jog foward (CW)" 0x2631:010
(P400.10) function.
• The frequency setpoint preset 6 is also used for the "Jog reverse (CCW)" 0x2631:011
(P400.11) function.