EasyManua.ls Logo

Emotron VS10 - Page 397

Emotron VS10
528 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The following signal flow shows the internal setpoint logics:
Notes:
In case of an activated network control, the functions for setpoint change-over are not
active! If in case of network control no setpoint is defined via the network control
word, the standard setpoint source is active.
The setpoint used by the motor control depends on the operating mode selected in
0x6060 (P301.00):
"MS: Velocity mode [-2]": The active frequency setpoint is used. In addition, the
PID
control can be activated in 0x4020:001 (P600.01).Configuring the process
control-
ler
232
"MS: Torque mode [-1]": The active torque setpoint is used.
Torque control w/
freq.
limit
147
"CiA: Velocity mode [2]": The setpoint speed defined via the "Target velocity"
0x6042 (P781.00) parameter is used.
Device profile CiA 402
299
As only one setpoint source can be active at a time, priorities are assigned to the
frequency, PID and torque setpoint sources. For details see the following subchapter
"Priority of the setpoint sources".
380.
Diagnostic parameters:
0x282B:002 (P125.02): Active setpoint source

Table of Contents

Other manuals for Emotron VS10

Related product manuals