13.3. 1/3-phase mains connection 230/240 V
Emotron VS30 inverters do not have an integrated EMC filter in the AC mains
supply.
In order to comply with the EMC requirements according to EN 61800−3, an
external EMC filter according to IEC EN 60939 has to be used.
The user must prove that the EN 61800−3 requirements for conformity are
fulfilled.
13.3.1. Rated data
The output currents apply to these operating conditions:
• At a switching frequency of 2 kHz or 4 kHz: Max. ambient temperature 45°C.
• At a switching frequency of 8 kHz or 16 kHz: Max. ambient temperature 40 °C.
VS30-23-1P7 VS30-23-2P4 VS30-23-3P2 VS30-23-4P2 VS30-23-6P0 VS30-23-7P0 VS30-23-9P6
0.25 0.37 0.55 0.75 1.1 1.5 2.2
1/N/PE AC 170 V ... 264 V, 45 Hz ... 65 Hz
3/PE AC 170 V ... 264 V, 45 Hz ... 65 Hz
Max. output current during the
recovery time
1.3 1.8 2.4 3.2 4.5 5.3 7.2
Max. output current during the
A
1.3 1.8 2.4 3.2 4.5 5.3 7.2
Max. motor cable length shielded