178 01-6203-01R3, CG Drives & Automation
Parameter
Name / value range / [default setting]
Info
0x6073
(P324.00)
Max current
(Max current)
0.0 ... [200.0] ... 3000.0 %
Maximum overload current of the inverter.
100 % ≡ Motor rated current 0x6075 (P323.00)
If the current consumption of the motor exceeds this current limit,
the
inverter changes its dynamic behaviour, in order to counteract this
exceedance.
If the change in the dynamic behaviour carried out by the inverter
does not result in exiting the overcurrent state, the inverter outputs
an error.
Note!
This parameter is not identical to the so-called ultimate motor current
I
ULT
!
The ultimate motor current set in 0x2D46:001 (P353.01) is a limit
value for synchronous motors that serves to protect their magnets.
The value to be set here should always be considerably below the
ulti
mate motor current!
0x2D88
(P104.00)
Motor current
(Motor current)
Read only: x.x A
Display des present current-r.m.s. value.
0x6078
(P103.00)
Current actual value
(Current actual)
Read only: x.x %
Display of the present motor current.
100 % ≡ Motor rated current 0x6075 (P323.00)