Error code
Info
Error type
Adjustable in
dec
hex
Keypad display
Error message
12816
0x3210
DC Bus OV
DC bus overvoltage
Fault
-
The DC-bus voltage of the inverter has exceeded the error threshold for overvoltage.
The error threshold results from the setting of the rated mains voltage in
0x2540:001 (P208.01).
Mains voltage
90
Notes:
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).
12817
0x3211
Warn.DC Bus OV
DC bus overvoltage warning
Warning
-
The DC-bus voltage of the inverter has exceeded the warning threshold for overvoltage set
in 0x2540:005 (P208.05).
Mains voltage
90
Notes:
Logging only (Error history buffer/Logbook)
12832
0x3220
DC Bus UV
DC bus undervoltage
Trouble
-
The DC-bus voltage of the inverter has fallen below the error threshold for undervoltage.
The error threshold results from the setting of the rated mains voltage in 0x2540:001
(P208.01).
Mains voltage
90
12833
0x3221
Warn.DC Bus UV
DC bus undervoltage warning
Warning
-
The DC-bus voltage of the inverter has fallen below the warning threshold for
undervoltage set in 0x2540:002 (P208.02).
Mains voltage
90
Notes:
Logging only (Error history buffer/Logbook)
12834
0x3222
DC-bus on-UV
DC-bus voltage to low for power up
Warning
-
Notes:
Logging only (Error history buffer/Logbook)
16912
0x4210
PU Overtemp.
PU: overtemperature fault
Fault
-
Temperature monitoring of the power unit has been triggered.
Possible causes:
Ambient temperature too high.
Fan or ventilation slots are polluted.
Fan is defective.
Remedies:
Provide for a sufficient cooling of the device.
Clean fan and ventilation slots.
If required, replace fan.
Set a variable switching frequency in for the inverter. The switching frequency is then
automatically reduced if the output current or temperature of the power unit are too
high.
17024
0x4280
Heatsink sensor
Heat sink temperature sensor fault
Fault
-
The sensor for temperature monitoring of the power unit provides implausible measured
values. This indicates a hardware defect of the sensor.
As a result of the failure of the temperature monitoring, there is a risk of fire by
overheating!
This error cannot be corrected by the user
à
Consultation with the manufacturer is
required.
17025
0x4281
Heatsink fan
Heat sink fan warning
Warning
-
Notes:
Logging only (Error history buffer/Logbook)
17029
0x4285
Warn.PU Overtemp
PU overtemperature warning
Warning
-
The temperature of the power section has exceeded the warning threshold for
overtemperature.
Notes:
Logging only (Error history buffer/Logbook)
17168
0x4310
Overtemp. motor
Motor temperature error
Fault
-
Notes:
The error can only be reset after a blocking time of 5 s.