REV 0, June 2005 Page 317
Operation Manual SUPREMA
12. Sensor Data Sheets
Short-circuit at Wire
max. cable length -X1/1/-X1/2
Failure indication XX
Short-circuit at the Wire
MAT-(TS)-Module -X1/1/-X1/2
Failure indication XX
Open-circuit at Wire Wire
max. cable length -X1/1 -X1/2
Failure indication X X
Open or Short Circuit Fault Indication:
X = Signal failure (FAIL-LED)
XX = Alarm LEDs, Signal exceeded, Signal failure (FAIL-LED)
Open-circuit at the Wire Wire Disconnect plug
MAT-(TS)-Module -X1/1 -X1/2 of MAT-(TS)
Failure indication X X X
Startup: The input modules (MCI 10) are presetted at 4 ... 20 mA.
Check with the sensor simulation module possible
After startup, longer dead periods and sensor changes, the warm-up period of the
electrochemical sensors is 3 hours minimum.
Warm-up periods: For O
2
< 60 s according to EN 50104: The warm-up periods are depending on the
component and can be seen in the list of components.
Function test: Application of span gas or reference gas via: PK 10 resp. PV 10 (1 l/min)
Calibration: Depending on component (according to list of components)
Approved measuring components, calibrating conditions, measuring ranges, alarm
levels and codes see list of components: D 0742 E 458
Possible other measuring components on request.