EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 1062

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.24
SEL-400 Series Relays Instruction Manual Date Code 20171006
Monitoring
Station DC Battery System Monitor
trol Voltage Supply” (Section 6.5) as an alternating component (ripple) of 5 per-
cent peak or less. (This definition is valid if the minimum instantaneous voltage
is not less than 80 percent of the rated voltage.) The relay measures ac ripple as a
peak-to-peak waveform, consequently, DC1RP and DC2RP should be set at or
greater than 10 percent (2 • 5% peak) of the equalizing voltage. Table 8 .10 shows
the ac ripple threshold settings for this example.
DC Ground
If a battery system is centered around chassis ground, then the magnitude of the
voltage measured from the positive terminal to ground and from the negative ter-
minal of the battery to ground should be approximately one-half of the nominal
battery system voltage. The ratio of the positive-to-ground battery voltage to the
negative-to-ground battery voltage is 1 to 1, or 1.00. Equation 8.5 is the balanced
(no grounding) ratio for a 125-Vdc battery system.
Equation 8.5
If either terminal is partially or completely shorted to chassis ground, then the
terminal voltage will be less than the nominal terminal-to-ground voltage. This
causes the ratio of positive voltage to negative voltage to differ from 1.00.
Equation 8.6 is an example of the unbalanced (grounding) ratio for a partial short
circuit to ground on the negative side of a 125-Vdc battery system.
Equation 8.6
The relay uses this voltage ratio to calculate a ground detection factor.
Figure 8.13 shows a graphical representation of the ground detection factor set-
ting and battery system performance.
Table 8.10 Example DC Battery Monitor Settings—AC Ripple Voltages
Setting Description Indication Value (Vac)
DC1RP AC ripple threshold, Mon. 1 Charger malfunction 14
DC2RP AC ripple threshold, Mon. 2 Charger malfunction 6
k
Vdc1
pos
Vdc1
neg
---------------------
62.50 V
62.50 V
------------------- 1.00===
k
Vdc1
pos
Vdc1
neg
---------------------
62.50 V
59.10 V
------------------- 1.06===

Table of Contents

Related product manuals