EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 1155

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.13
Date Code 20171006 Instruction Manual SEL-400 Series Relays
Settings
Port Settings
Make Table 12.20 settings if Port setting PROTO := RTD.
RMB2PU RMB2 Pickup Time (1–8 messages) 1
RMB2DO RMB2 Dropout Time (1–8 messages) 1
RMB3FL RMB3 Channel Fail State (0, 1, P) P
RMB3PU RMB3 Pickup Time (1–8 messages) 1
RMB3DO RMB3 Dropout Time (1–8 messages) 1
RMB4FL RMB4 Channel Fail State (0, 1, P) P
RMB4PU RMB4 Pickup Time (1–8 messages) 1
RMB4DO RMB4 Dropout Time (1–8 messages) 1
RMB5FL RMB5 Channel Fail State (0, 1, P) P
RMB5PU RMB5 Pickup Time (1–8 messages) 1
RMB5DO RMB5 Dropout Time (1–8 messages) 1
RMB6FL RMB6 Channel Fail State (0, 1, P) P
RMB6PU RMB6 Pickup Time (1–8 messages) 1
RMB6DO RMB6 Dropout Time (1–8 messages) 1
RMB7FL RMB7 Channel Fail State (0, 1, P) P
RMB7PU RMB7 Pickup Time (1–8 messages) 1
RMB7DO RMB7 Dropout Time (1–8 messages) 1
RMB8FL RMB8 Channel Fail State (0, 1, P) P
RMB8PU RMB8 Pickup Time (1–8 messages) 1
RMB8DO RMB8 Dropout Time (1–8 messages) 1
MBTIME Accept M
IRRORED BITS Time Synchronization (Y, N) N
MBNUMAN Number of Analog Channels (0–7) 0
MBANA1 Selection for Analog Channel 1 (analog label)
a
MBANA2 Selection for Analog Channel 2 (analog label)
a
MBANA3 Selection for Analog Channel 3 (analog label)
a
MBANA4 Selection for Analog Channel 4 (analog label)
a
MBANA5 Selection for Analog Channel 5 (analog label)
a
MBANA6 Selection for Analog Channel 6 (analog label)
a
MBANA7 Selection for Analog Channel 7 (analog label)
a
MBNUMVT Number of Virtual Terminal Channels (OFF, 0–7) OFF
a
The default value of the MBANA
n
settings is relay specific. See the product-specific instruction
manual to find these defaults.
Table 12.20 RTD Protocol Settings
Label Prompt Default Value
RTDNUM RTD Number of Inputs (0–12) 12
RTDnTY
a
a
Where n is the number of RTD inputs enabled in the RTDNUM setting.
RTD n Type (NA, PT100, NI100, NI120, CU10)
b
b
NA designates an input that is not connected to an RTD device.
PT100
Ta b l e 1 2.1 9 M
IRRORED BITS Protocol Settings (Sheet 2 of 2)
Label Prompt Default Value

Table of Contents

Related product manuals