NTP—Current STRATUM status of this SecureSync unit.
TemperatureThe current board temperature will be displayed here, plus—depending
on product configuration—oscillator, and CPU temperatures, as well. For more inform-
ation, see "Temperature Management" on page297.
Reference Status panel
REFERENCE: Indicates the name type of each reference. These are determined by the
inputs set up for the SecureSync
PRIORITY: Indicates the priority of each reference. This number will be between 1 and
15. References in this panel appear in their order of priority. See "Configuring Input
Reference Priorities" on page163 for more information.
STATUS: Indicates which available input reference is acting as the Time reference and
which available input reference is acting as the 1PPS reference.
Green indicates that the reference is present and has been declared valid.
Orange indicates the input reference is not currently present or is not currently
valid.
PHASE: The measured time interval error ("TIE") between the internally disciplined 1PPS
and the selected external 1PPS reference.
Performance panel
Disciplining StateIndicates whether or not the internal oscillator is currently being dis-
ciplined (steered to an input reference).
1PPS Phase Error—An internal measurement (in nanoseconds) of the internal 1PPSs’
phase error with respect to the selected input reference (if the input reference has excess-
ive jitter, phase error will be higher)
10MHz Frequency ErrorAn internal estimated calculation (in Hertz) of the internal oscil-
lator’s frequency error, based on the phase accuracy error at the beginning and end of
a frequency measurement window (the length of this window will vary depending upon
the type of oscillator installed and the oscillator adjustment algorithm).
Events panel
The Events panel in the bottom-left corner of the HOME screen is a log of SecureSyncs recent
activity. It updates in real time.
Note: If you know the individual reference or output whose status you wish to see,
you can access the Status window of that reference or output directly through the
INTERFACES > REFERENCES or INTERFACES > OUTPUTS drop-down menu.
278
CHAPTER 4 SecureSync User Reference Guide Rev. 26
4.5 Quality Management

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Spectracom SecureSync and is the answer not in the manual?

Spectracom SecureSync Specifications

General IconGeneral
ModelSecureSync
Time ReferenceGPS, GLONASS, BeiDou, Galileo, IRIG, NTP, PTP, 1PPS
DisciplinesGNSS, IRIG, PTP, NTP, SyncE
InputsGPS, GLONASS, BeiDou, Galileo, IRIG, NTP, PTP, 1PPS
OutputsNTP, PTP, 1PPS, IRIG
ProtocolsPTP, NTP, SNMP, SSH, HTTPS
Form Factor1U Rack-mount
RedundancyOptional redundant power supply
Security FeaturesPassword protection, access control lists, SSH, HTTPS, SNMPv3, NTP authentication, PTP authentication
Power Supply100-240 VAC, 50-60 Hz
Operating Temperature0°C to +50°C
Dimensions44.45 mm (H) x 482.6 mm (W)