126 Rockwell Automation Publication 2198-UM004A-EN-P - October 2019
Chapter 7 Configure the Drive with KNX5100C Software
After Motor NV is selected and the drive power cycles, these other changes are
made:
Commutation alignment is fixed as Motor offset (A in next figure)
The default Startup Method is set as Incremental (B in next figure)
The position feedback is zero
You can change the startup method to Absolute from the pull-down menu. If you
do, click Download to initiate the change. Then parameter ID242 (P2.069)
AbsoluteSystemSetting is set to 1 and the drive automatically triggers a power
cycle. Warning A 06A (Absolute position is not initialized) occurs after the
power cycle, so you must initialize the absolute position to clear this fault to let
the absolute operation start.