Rockwell Automation Publication 2198-UM004A-EN-P - October 2019 453
Upgrade the Drive Firmware Appendix B
12. Click Yes (only if you are ready).
The Progress dialog box appears and the update begins.
The state on the display changes
from STDBY (STANDBY), or
STOP (STOPPED) to F_UPD
(FIRMWARE UPDATE), which
indicates that the upgrade is in
progress.
After the upgrade information is
sent to the drive, the drive resets and
performs diagnostic checking.
13. Wait for the Progress dialog box to time out.
It is normal for this process to take several minutes.
14. Verify that the Update Status dialog box appears and indicates success or
failure as described below.
15. Click OK.
IMPORTANT Do not cycle power to the drive during this process or the firmware
upgrade does not complete successfully.
Upgrading Status If
Success Update complete appears in a GREEN Status dialog box, then go to step 15
.
Failure Update failure appears in a RED Status dialog box, then see the ControlFLASH
Firmware Upgrade Software User Manual, publication 1756-UM105
for
troubleshooting information.
IMPORTANT: If the power is lost during the firmware upgrade, the update fails. When
the power is restored, three different situations happen depending on when the
power went off.
Panel display shows UPt 1: Update the firmware again.
Panel display is blank:, The drive automatically finishes the last firmware update in
20 seconds, then it resets to complete the update.
Panel display shows UPt 3: Update the firmware again.