Name / value range / [default setting]
(P337.02)
Negative torque limit source
(Neg. torqlim src)
Selection of the source for the negative torque limit source.
Negative torque limit source = (-) Max torque 0x6072 (P326.00).
Negative torque limit source = 0.0 %.
The negative torque limit source is defined as analog signal via the
analog input 1.
Analog input 1
423
The negative torque limit source is defined as analog signal via the
analog input 2.
Analog input 2
427
Negative torque limit source = Negative torque limit 0x60E1.
The negative torque limit source is defined as process data object via
network.
Configuring the network
166
(P300.00)
(Motor ctrl mode)
•
Setting can only be changed if the inverter is
inhibi
ted.
Selection of the motor control type.
Sensorless control (SL PSM)
(from
version 02.00)
This control type is used for the sensorless control of a synchronous
motor.
Sensorless control for synchronous motors (SL-PSM)
118
Sensorless vector control (SLVC)
This control type is used for sensorless vector control of an
asynchronous motor.
Sensorless vector control (SLVC)
115
V/f characteristic control (VFC open loop)
This control mode is used for the speed control of an asynchronous
motor via a V/f characteristic and is the simplest control mode.
V/f characteristic control (VFC)
110
0.0 ... [250.0] ... 3276.7 %
Positive torque limit source for speed control with torque limitation.
•
100 % ≡ Motor rated torque 0x6076 (P325.00)
0.0 ... [250.0] ... 3276.7 %
Negative torque limit source for speed control with torque limitation.
•
100 % ≡ Motor rated torque 0x6076 (P325.00)
Next steps
•
The inverter provides different functions by means of which the drive behaviour can
be further optimised.
Optimisation of motor control
122
•
The default setting enables the operation of a power-adapted motor.
An optimum
operation of this motor control type requires an optimisation of the control loops!
Optimisation of the control loops
133