EasyManuals Logo

Emotron VS10 User Manual

Emotron VS10
528 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #243 background imageLoading...
Page #243 background image
Predefined Modbus status registers
These registers are only provided with read access.
The cross-reference in column 2 leads to the detailed parameter description.
Modbus registers
Permanently assigned parameter
Address
Name
42001
0x400C:001 (P593.01)
AC Drive status word
42002
0x400C:006 (P593.06)
Frequency (0.01)
42003
0x603F (P150.00)
Error code
42004
0x400C:005 (P593.05)
Drive status
42005
0x2D89 (P106.00)
Motor voltage
42006
0x2D88 (P104.00)
Motor current
42007
0x6078 (P103.00)
Current actual value
42008
0x2DA2:002 (P108.02)
Apparent power
(42008 = High Word, 42009 = Low Word)
42009
42010
0x2D84:001 (P117.01)
Heatsink temperature
42011
0x2D87 (P105.00)
DC-bus voltage
42012
0x60FD (P118.00)
Digital inputs (only bit 16 ... bit 31)
42013
0x6077 (P107.00)
Torque actual value
42014 ... 42021
-
Reserved
Parameter
Name / value range / [default setting]
Info
0x232B:001
(P530.01)
Modbus parameter mapping: Parameter 1
(Para. mapping: Parameter 1)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40103.
0x232B:002
(P530.02)
Modbus parameter mapping: Parameter 2
(Para. mapping: Parameter 2)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40105.
0x232B:003
(P530.03)
Modbus parameter mapping: Parameter 3
(Para. mapping: Parameter 3)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40107.
0x232B:004
(P530.04)
Modbus parameter mapping: Parameter 4
(Para. mapping: Parameter 4)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40109.
0x232B:005
(P530.05)
Modbus parameter mapping: Parameter 5
(Para. mapping: Parameter 5)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40111.
0x232B:006
(P530.06)
Modbus parameter mapping: Parameter 6
(Para. mapping: Parameter 6)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40113.
0x232B:007
(P530.07)
Modbus parameter mapping: Parameter 7
(Para. mapping: Parameter 7)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40115.
0x232B:008
(P530.08)
Modbus parameter mapping: Parameter 8
(Para. mapping: Parameter 8)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40117.
0x232B:009
(P530.09)
Modbus parameter mapping: Parameter 9
(Para. mapping: Parameter 9)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40119.
0x232B:010
(P530.10)
Modbus parameter mapping: Parameter 10
(Para. mapping: Parameter 10)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40121.
0x232B:011
(P530.11)
Modbus parameter mapping: Parameter 11
(Para. mapping: Parameter 11)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40123.
0x232B:012
(P530.12)
Modbus parameter mapping: Parameter 12
(Para. mapping: Parameter 12)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40125.
0x232B:013
(P530.13)
Modbus parameter mapping: Parameter 13
(Para. mapping: Parameter 13)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entry for Modbus register 40127.

Table of Contents

Other manuals for Emotron VS10

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emotron VS10 and is the answer not in the manual?

Emotron VS10 Specifications

General IconGeneral
BrandEmotron
ModelVS10
CategoryController
LanguageEnglish

Related product manuals