Error code
Info
Error type
Adjustable in
dec
hex
Keypad display
Error message
65334
0xFF36
BrkResistor OL.W
Brake resistor: overload warning
Warning
-
Error message is not available for the inverter Emotron VS10/30.
Notes:
When the error type is set to "Warning", only logging takes place (Error history buffer/
Logbook)
65335
0xFF37
Auto start disab
Automatic start disabled
Fault
-
When the mains power was switched on, there was already a start command and the
automatic start at power-up is set to "Off [0]" in 0x2838:002 (P203.02).
Remedy:
Deactivate start command and reset error.
65366
0xFF56
Max. motor freq.
Maximum motor frequency reached
Warning
-
The maximum motor speed set in 0x6080 (P322.00) is active.
Notes:
Logging only (Error history buffer/Logbook)
65413
0xFF85
Keypad full ctrl
Keypad full control active
Warning
-
The "Keypad Full Control" control mode is active. Both the control and the setpoint
selection are made via the keypad. A renewed click of the keypad key
CTRL
serves to
stop the control mode again.
Keypad Configuration of R/F and CTRL buttons
248
Notes:
Logging only (Error history buffer/Logbook)