486 01-6203-01R3, CG Drives & Automation
The maximum possible torque has been reached and the deceleration time set in
0x2D67:002 (P329.02) has elapsed.
Motor torque monitoring
164
The keypad was removed while the keypad control was activated.
Remedy:
Plug on the keypad again or
activate another control source.
Control source change-over
358
Brake resistor: overload fault
Error message is not available for the inverter Emotron VS10/30.
Notes:
The error can only be reset after a blocking time of 5 s.
Notes:
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).
The error can only be reset by mains switching.
(P350.02)
The motor speed has reached the error threshold for overspeed set in .
Motor speed monitoring
164
Notes:
The error can only be reset after a blocking time of 1 s.
(P310.01)
A failure of several motor phases has been detected.
Remedy:
Check wiring between inverter and motor.
In case of a false tripping, adapt the settings for the motor phase failure detection.
Motor phase failure detection
163
Notes:
The error can only be reset after a blocking time of 2 s.
Motor phase failure phase U
(P310.01)
A failure of the motor phase U has been detected.
Remedy:
Check wiring between inverter and motor.
In case of a false tripping, adapt the settings for the motor phase failure detection.
Motor phase failure detection
163
Notes:
The error can only be reset after a blocking time of 2 s.
Motor phase failure phase V
(P310.01)
A failure of the motor phase V has been detected.
Remedy:
Check wiring between inverter and motor.
In case of a false tripping, adapt the settings for the motor phase failure detection.
Motor phase failure detection
163
Notes:
The error can only be reset after a blocking time of 2 s.
Motor phase failure phase W
(P310.01)
A failure of the motor phase W has been detected.
Remedy:
Check wiring between inverter and motor.
In case of a false tripping, adapt the settings for the motor phase failure detection.
Motor phase failure detection
163
Notes:
The error can only be reset after a blocking time of 2 s.
Motor parameter identification fault