Error code
Info
Error type
Adjustable in
dec
hex
Keypad display
Error message
30359
0x7697
Parameter loss
Parameter changes lost
Fault
-
Changed parameter settings got lost due to the removal of the 24-V voltage supply.
In order to reset the error, there are the following options:
Execute device command "Load default settings" 0x2022:001 (P700.01).
Execute device command "Save user data" 0x2022:003 (P700.03).
Switch inverter off and on again without plugged-in USB module.
Notes:
Serious error: The inverter is inhibited immediately. The motor becomes torqueless
(coasts).
33045
0x8115
Time-out (PAM)
Time-out (PAM)
No response
0x2552:004
(P595.04)
The parameter access monitoring has been triggered.
Parameter access monitoring (PAM)
196
33154
0x8182
CAN bus off
CAN: bus off
Trouble
0x2857:010
A change to the "Bus-Off" state has been made.
33155
0x8183
CAN bus warning
CAN: warning
Warning
0x2857:011
Notes:
When the error type is set to "Warning", only logging takes place (Error history buffer/
Logbook)
33156
0x8184
CAN heartb. C1
CAN: heartbeat time-out consumer 1
Fault
0x2857:005
CANopen heartbeat protocol
202
33157
0x8185
CAN heartb. C2
CAN: heartbeat time-out consumer 2
Fault
0x2857:006
CANopen heartbeat protocol
202
33158
0x8186
CAN heartb. C3
CAN: heartbeat time-out consumer 3
Fault
0x2857:007
CANopen heartbeat protocol
202
33159
0x8187
CAN heartb. C4
CAN: heartbeat time-out consumer 4
Fault
0x2857:008
CANopen heartbeat protocol
202
33168
0x8190
Watchdog timeout
Network: watchdog timeout
Fault
-
33170
0x8192
Net. Init. error
Network: initialisation error
Fault
-
33171 0x8193
Inv. cyclic data
Network: invalid cyclic process data
Trouble
-
33184 0x81A0
Modbus TX error
Modbus transmit message error
Warning
-
Notes:
Logging only (Error history buffer/Logbook)
33185
0x81A1
Modbus time-out
Modbus: network time-out
Fault
0x2858:001
(P515.01)
No valid messages have been received via the Modbus for a longer time than the time-out
time set in 0x2858:002 (P515.02).
33186
0x81A2
Modbus request
Modbus: incorrect request by master
Warning
-
Notes:
Logging only (Error history buffer/Logbook)
33414
0x8286
PDO map error
Network: PDO mapping error
Fault
-
33425
0x8291
Timeout RPDO1
CAN: RPDO1 time-out
Fault
0x2857:001
The RPDO was not received within the monitoring time set for the RPDO or not with the
configured sync.
CANopen process data objects
204
33426
0x8292
Timeout RPDO2
CAN: RPDO2 time-out
Fault
0x2857:002
The RPDO was not received within the monitoring time set for the RPDO or not with the
configured sync.
CANopen process data objects
204
33427
0x8293
Timeout RPDO3
CAN: RPDO3 time-out
Fault
0x2857:003
The RPDO was not received within the monitoring time set for the RPDO or not with the
configured sync.
CANopen process data objects
204
33553
0x8311
Torque limit
Torque limit reached
No response
0x2D67:001

Table of Contents