484 01-6203-01R3, CG Drives & Automation
Error code
Info
Error type
Adjustable in
dec
hex
Keypad display
Error message
30346
0x768A
Wrong EPM
Memory module: wrong type
Fault
-
The plugged-in memory module is not supported by the inverter. The default setting saved
in the inverter firmware is loaded. The error cannot be reset by the user.
Remedy:
Switch off inverter.
Replace plugged-in memory module by a memory module that matches the inverter.
Switch the inverter on again.
30352
0x7690
EPM-FW incomp.
EPM firmware version incompatible
Fault
-
The parameter settings saved in the memory module do not match the firmware version.
The data are loaded into the RAM memory, but are incompatible.
Remedy:
Execute device command "Load default settings" 0x2022:001 (P700.01).
Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data"
0x2022:006 (P700.06) in order that the error does not occur at the next switch-on.
30353
0x7691
EPM: FW incomp.
EPM data: firmware type incompatible
Fault
-
The parameter settings saved in the memory module do not match the firmware type. The
data are loaded into the RAM memory, but are incompatible.
Remedy:
Execute device command "Load default settings" 0x2022:001 (P700.01).
Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data"
0x2022:006 (P700.06) in order that the error does not occur at the next switch-on.
30354
0x7692
UserCU not match
EPM data: new firmware type detected
Fault
-
The parameter settings saved in the memory module do not match in the inverter
hardware. The data is loaded into the RAM memory and is compatible. However, the
settings must be accepted by the user:
Reset error.
Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data"
0x2022:006 (P700.06) in order that the error does not occur at the next switch-on.
Alternatively, the default setting can be loaded and then saved.
30355
0x7693
EPM PU size inco
EPM data: PU size incompatible
Fault
-
The parameter settings saved in the memory module do not match the power unit. The
data are loaded into the RAM memory, but are incompatible.
Remedy:
Execute device command "Load default settings" 0x2022:001 (P700.01).
Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data"
0x2022:006 (P700.06) in order that the error does not occur at the next switch-on.
30356
0x7694
EPM new PU size
EPM data: new PU size detected
Fault
-
The parameter settings saved in the memory module do not match in the inverter
hardware. The data is loaded into the RAM memory and is compatible. However, the
settings must be accepted by the user:
Reset error.
Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data"
0x2022:006 (P700.06) in order that the error does not occur at the next switch-on.
Alternatively, the default setting can be loaded and then saved.
30357
0x7695
InvalidChgovrCfg
Invalid parameter changeover configuration
Warning
-
One or several parameters cannot be used for the "parameter change-over" function. The
parameter change-over is deactivated.
Remedy:
Check error message for parameter change-over in 0x4047:001 (P756.01) and correct
the list entry displayed in 0x4047:002 (P756.02).
Notes:
Logging only (Error history buffer/Logbook)
30358
0x7696
Unkn. Par in EPM
EPM data: unknown parameter found
Info
-
The memory module contains parameter settings for one or several parameters that are
not known to the inverter.
Remedy: Execute device command "Save user data" 0x2022:003 (P700.03). This reinitialises
the user memory with the current parameter settings. By this means, parameter settings
no longer required are deleted automatically.
Notes:
Information only.