312 01-6203-01R3, CG Drives & Automation
Name / value range / [default setting]
(P756.01)
Parameter change-over error message: Status
(PSet error msg.: Status)
Error message for the "parameter change-over" function.
In the event of an error, an error status is shown here, and in
0x4047:002 (P756.02) the number of the list entry in which the error
has occurred is displayed (in connection with the value set selected).
If several errors occur at the same time, only the first incorrect list
entry
will be displayed. Hence, after elimination of the displayed error and
repeated activation, more errors may be displayed.
The parameter list will always be processed from beginning to end,
even if errors occur in the meantime.
33806
Invalid index
33815
Writing impermissible
(P756.02)
Parameter change-over error message: List entry
(PSet error msg.: List entry)
Read only
Error message for the "Parameter set changeover" function.
In the event of an error, the number of the list entry for which the
error displayed in 0x4047:001 (P756.01) has occurred is shown here.
(P400.40)
Function list: Load parameter set
(Function list: Load param.set)
Setting can only be changed if the inverter is
inhibi
ted.
For further possible settings, see parameter
0x2631:001 (P400.01).
364
Assignment of a trigger for the "Load parameter set" function.
Trigger = FALSE-TRUE edge: parameter change-over to the value set
selected via "Select parameter set (bit 0)" and "Select parameter set (bit
1)".
Trigger = FALSE: no action.
Notes:
The activation method for the "Parameter change-over" function can
be selected in 0x4046 (P755.00).
No trigger assigned (trigger is constantly FALSE).
(P400.41)
Function list: Select parameter set (bit 0)
(Function list: Sel. paramset b0)
Setting can only be changed if the inverter is
inhibi
ted.
For further possible settings, see parameter
0x2631:001 (P400.01).
364
Assignment of a trigger for the "Select parameter set (bit 0)" function.
Selection bit with the valency 2
0
for "Parameter change-over" function.
Trigger = FALSE: selection bit = "0".
Trigger = TRUE: selection bit = "1".
No trigger assigned (trigger is constantly FALSE).
(P400.42)
Function list: Select parameter set (bit 1)
(Function list: Sel. paramset b1)
Setting can only be changed if the inverter is
inhibi
ted.
For further possible settings, see parameter
0x2631:001 (P400.01).
364
Assignment of a trigger for the "Select parameter set (bit 1)" function.
Selection bit with the valency 2
1
for "Parameter change-over" function.
Trigger = FALSE: selection bit = "0".
Trigger = TRUE: selection bit = "1".
No trigger assigned (trigger is constantly FALSE).