EasyManua.ls Logo

HAIMA 7 - Page 413

HAIMA 7
654 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service warnings
U-5
8. close all doors and windows.
9. measure ambient temperature and record
pressure readings at high-pressure and
low-pressure side of sst 49 c061 001.
10. verify that the intersection of pressure reading
of the sst 49 c061 001 and ambient temperature
is in the shaded zone. If not, diagnose and
eliminate the faults of cooling system. (refer to
section u, troubleshooting index)
High-pressure side
Low-pressure side
Ambient temperature
Pressure reading of manifold gauge

Table of Contents

Related product manuals