Under the System tab, you can set Notifications for Minor and Major Alarms/Clearances. The
temperature readouts used for the Alarms are generated by the CPU temperature sensor.
Also, you can set the temperature threshold value for Minor/Major alarms, and define a retry
value by determining how many readings (1/min.) the temperature must exceed the threshold
value before an alarm/clearance is triggered.
The default temperature threshold value for both Minor, and Major Alarms is 100°C. With sim-
ultaneous alarm triggerings, the Major Alarm will override the Minor Alarm, i.e. you will be
notified only about the Major Alarm. If you want to be notified early about a rise in tem-
perature, a recommended setting for the Minor Alarm temperature would be 90°C. Please note
that it is not advisable to set the Major Alarm temperature to a value higher than 100°C.