346 TimeProvider 5000 Users Guide 098-00028-000 Revision F – May, 2012
Chapter 4 Provisioning
Provisioning Alarms
Example
1. Login at the Admin or Config-user level (see Logging In, on page 275).
2. Type
show ref and press Enter to check the reference mode.
3. Type
set ref mode frequency and press Enter.
4. Type
set clock date-time <value> and press Enter. Enter the value in
format yyyy-mm-dd,hh:mm:ss.
5. Type
sync tod-source now and press Enter.
Provisioning Alarms
This section describes the commands used to provision and manage alarms in the
TimeProvider 5000. The user can provision the alarms to be enabled or disabled
and set thresholds to turn the alarms on and off. For a list of all alarms, see
Appendix A, System Messages.
Software commands allow you to perform the following:
Provision the severity level
Provision the alarm (enable or disable)
Show current alarm settings
Show current alarms
Display alarm status
Alarms are also indicated by LEDs on the IOC and IMC modules.
Note: Disabling an input port will clear all alarms and events related
to the port.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeProvider 5000 and is the answer not in the manual?

Symmetricom TimeProvider 5000 Specifications

General IconGeneral
BrandSymmetricom
ModelTimeProvider 5000
CategoryServer
LanguageEnglish

Related product manuals