168 01-6203-01R3, CG Drives & Automation
Parameter
Name / value range / [default setting]
Info
0x2946:003
(P340.03)
Speed limitation: Upper speed limit source
(Speed limitation: Uppspeed lim src)
From version 03.00
Selection of the source for the upper speed limit.
0
Maximum frequency
Upper speed limit = Maximum frequency 0x2916 (P211.00).
1
Fixed Limit 0.0 Hz
Upper speed limit = 0.0 Hz.
2
Analog input 1
The upper speed limit is defined as analog signal via the analog input 1.
Analog input 1
423
3
Analog input 2
The upper speed limit is defined as analog signal via the analog input 2.
Analog input 2
427
4
Upper speed limit [Hz]
Upper speed limit = setting in 0x2946:005 (P340.05) in [Hz].
5
Upper speed limit
Upper speed limit = setting in 0x2946:001 (P340.01) in [vel. unit].
6
Network target velocity
The upper speed limit is defined as process data object via network.
Configuring the network
166
0x2946:004
(P340.04)
Speed limitation: Lower speed limit source
(Speed limitation: Lowspeed lim src)
From version 03.00
Selection of the source for the lower speed limit.
0
(-) Maximum frequency
Lower speed limit = (-) Maximum frequency 0x2916 (P211.00).
1
Fixed Limit 0.0 Hz
Lower speed limit = 0.0 Hz.
2
Analog input 1
The lower speed limit is defined as analog signal via the analog input 1.
Analog input 1
423
3
Analog input 2
The lower speed limit is defined as analog signal via the analog input 2.
Analog input 2
427
4
Lower frequency limit
Lower speed limit = setting in 0x2946:006 (P340.06) in [Hz].
5
Lower speed limit
Lower speed limit = setting in 0x2946:002 (P340.02) in [vel. unit].
6
Network target velocity
The lower speed limit is defined as process data object via network.
Configuring the network
166
0x2946:005
(P340.05)
Speed limitation: Upper frequency limit
(Speed limitation: Upper freq.limit)
Device for 50-Hz mains: -1000.0 ... [50.0] ... 1000.0 Hz
Device for 60-Hz mains: -1000.0 ... [60.0] ... 1000.0 Hz
From version 03.00
Upper limit for the speed limitation.
Setting is only effective with the selection "Lower frequency limit [4]"
in
0x2946:004 (P340.04).
0x2946:006
(P340.06)
Speed limitation: Lower frequency limit
(Speed limitation: Lower freq.limit)
Device for 50-Hz mains: -1000.0 ... [-50.0] ...
1000.0 Hz
Device for 60-Hz mains: -1000.0 ... [-60.0] ...
1000.0 Hz
From version 03.00
Lower limit for speed limitation.
Setting is only effective with the selection "Lower frequency limit [4]"
in
0x2946:004 (P340.04).
0x2946:007
(P340.07)
Speed limitation: Actual upper speed limit
(Speed limitation: Act uppspeed lim)
Read only: x.x Hz
From version 03.00
Display of the current upper limit for speed limitation.
0x2946:008
(P340.08)
Speed limitation: Actual lower speed limit
(Speed limitation: Act lowspeed lim)
Read only: x.x Hz
From version 03.00
Display of the current lower limit for speed limitation.
0x2948:002
(P336.02)
ramp time
(Ramp time)
0.0 ... [1.0] ... 60.0 s
From version 03.00
Ramp time for operating mode "MS: Torque mode".
The torque setpoint is led via a ramp generator. This provides for a
"smooth" switch-over between different setpoint sources.
The set ramp time refers to the ramping up/down of 0 ... 100 % rated
motor torque 0x6076 (P325.00)
. At a lower setpoint selection, the
ramp time is reduced accordingly.