288 01-6203-01R3, CG Drives & Automation
PIN1 setting
PIN2 setting
Log-in
Status display after
log-in
Active write access protection (via keypad/»Emotron Easy
starter«)
0x203D (P730.00)
0x203E (P731.00)
0x203F
0x2040 (P197.00)
> 0
> 0
0 or wrong PIN
1
No write access.
Correct PIN1
2
Write access only possible to favorites.
Correct PIN2
0
Write access to all parameters possible.
Access
PIN1 PIN2
Diagnostics (read access)
Favorites
All parameters
If PIN1 and PIN2 are set identically, a write access to all parameters is possible after the PIN has been
entered correctly.
Notes:
The firmware of the inverter does only support the protection status.
The access protection is realised by the keypad and engineering tools as "clients"
themselves based on the current protection status 0x2040 (P197.00).
More details on how to configure the write access protection with the respective client
can be found in the following subchapters:
Write access protection in the »Emotron Easy starter«
273
Write access protection in the keypad
276
Parameter
Name / value range / [default setting]
Info
0x203D
(P730.00)
PIN1 access protection
(PIN1 protection)
-1 ... [0] ... 9999
PIN definition for write access protection.
1 … 9999 = set/change PIN.
0 = delete PIN (deactivate access protection).
When the PIN has been set successfully, the value -1 is shown;
other
wise 0.
Setting/changing the PIN via keypad/»Emotron Easy starter« only
possible if
no write access protection is active.
Settings/changes via »Emotron Easy starter« become effective
immediately;
via keypad they only become effective when the
parameter group has been exited.
0x203E
(P731.00)
PIN2 access protection
(PIN2 protection)
-1 ... [0] ... 9999
0x203F
PIN1/PIN2 log-in
-32768 ... [0] ... 32767
Parameter for PIN entry for the purpose of deactivating an active access
protection temporarily.
1 … 9999 = log-in (deactivate access protection temporarily).
0 = log-out (reactivate access protection).
After having logged in successfully, the value 0 is shown; otherwise -1.
After 10 invalid entries, the log-in function is inhibited. In order to
remove the log-in inhibit, the inverter must be switched off and on
again.
0x2040
(P197.00)
Access protection status
(Protect. status)
Read only
Bit-coded display of the active access protection after login by PIN1/
PIN2.
Bit 0
No write access
Bit 1
Only favorites changeable

Table of Contents