Name / value range / [default setting]
(P400.40)
Function list: Load parameter set
(Function list: Load param.set)
Setting can only be changed if the inverter is
inhibi
ted.
For further possible settings, see parameter
0x2631:001 (P400.01).
364
Assignment of a trigger for the "Load parameter set" function.
Trigger = FALSE-TRUE edge: parameter change-over to the value set
selected via "Select parameter set (bit 0)" and "Select parameter set (bit
1)".
Trigger = FALSE: no action.
Notes:
The activation method for the "Parameter change-over" function can
be selected in 0x4046 (P755.00).
No trigger assigned (trigger is constantly FALSE).
(P400.41)
Function list: Select parameter set (bit 0)
(Function list: Sel. paramset b0)
Setting can only be changed if the inverter is
inhibi
ted.
For further possible settings, see parameter
0x2631:001 (P400.01).
364
Assignment of a trigger for the "Select parameter set (bit 0)" function.
Selection bit with the valency 2
0
for "Parameter change-over" function.
Trigger = FALSE: selection bit = "0".
Trigger = TRUE: selection bit = "1".
No trigger assigned (trigger is constantly FALSE).
(P400.42)
Function list: Select parameter set (bit 1)
(Function list: Sel. paramset b1)
Setting can only be changed if the inverter is
inhibi
ted.
For further possible settings, see parameter
0x2631:001 (P400.01).
364
Assignment of a trigger for the "Select parameter set (bit 1)" function.
Selection bit with the valency 2
1
for "Parameter change-over" function.
Trigger = FALSE: selection bit = "0".
Trigger = TRUE: selection bit = "1".
No trigger assigned (trigger is constantly FALSE).
(P755.00)
Activation of parameter set
(PSet activation)
Selection of the activation method for the parameter change-over.
If the selection is changed from "Via command... [0]/[1]" to "If the
selection is changed...[2]/[3]" after switch-on, the parameter set
selected via the functions "Select parameter set (bit 0)" and "Select
parameter set (bit 1)" is activated immediately. In case of selection
[2], however, this only takes place if the inverter is disabled, the motor
is stopped or an error is active.
Via command (disable required)
The parameter set selected via the functions "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is activated if the trigger assigned
to the "Load parameter set" function in
0x2631:040 (P400.40) provides a
FALSE-TRUE edge AND the inverter is inhibited, the motor is stopped or
Via command (immediately)
The parameter set selected via the functions "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is immediately activated if the
trigger assigned to the "Load parameter set" function in
0x2631:040
(P400.40) provides a FALSE-TRUE edge.
2
If the selection is changed (disable required)
The parameter set selected via the functions "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is activated if the state of these
selection bits changes AND the inverter is inhibited, the motor is
stopped or an error is active.
If the selection is changed (immediately)
The parameter set selected via the functions "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is activated immediately if the
state of these selection bits is changed.