Cordex®CXCHPControllerSoftwareManual|7-Invertersystems
7.7.1. Configure a basic bypass switch
Thefollowingdescribeshowtoconfigureabasicbypassswitch.IfthesiteisequippedwithanXMBS
bypassswitch,seethefollowingsection.
To configure the basic bypass switch:
1. GotoSystems > Inverter System > Inventory > Breakers, Fuses and Bypass Switches.
SelecttheAdd Bypass Switch button.Ifabypassswitchexists,butneedstoberemoved,select
Remove.
2. SelecttheGO TO buttonofthebypassswitchtoconfigure.
3. IntheBypass Switch table,settheName,Description andInput Source values.Whenthe
valueofdigitalinputsourceisActive,bypassisintheBypass state.WhenitisInactive,the
bypassisintheInverter state.Alternatively,selecttheConfigure Bypass Switch wizardtobe
promptedfortheessentialconfigurationrequiredforthebypassswitchtofunction.
4. IntheAlarms table,selecttheGO TO buttonoftheBypass Active alarmandconfigureas
required.
7.7.2. Configure an XMBS bypass switch
To configure the XMBS bypass switch:
1. GotoSystems > Inverter System > Inventory > Breakers, Fuses & Bypass Switches.Select
theAdd Bypass Switch with XMBS support wizard.
2. Inthewizard,determinewhethersignalssuchastheswitch'sbypassstatewillbetransmittedvia
CANorhardwiredI/O.CANSignalsistherecommendedconnectiontypewhenavailable.The
CANSignalsconnectiontypeisnotsupportedonXMBS(hardwarerevision1)devices.
3. Afterfinishingthewizard,selecttheGO TO buttonofthebypassswitchtoconfigure.
4. IftheXMBSbypassswitchsignalsaretobetransmittedviaHardwiredI/O,selecttheConfigure
XMBS Hardwired Signals wizardifithasnotbeenconfiguredalready.
5. IntheAlarms table,selecttheGO TO buttonofeachalarmandconfigureasrequired.
6. Iftheinvertersystemhasaninternalbypassswitch,GotoSystems > Inverter System >
Configure System andmaptheInternal Bypass Switch entryappropriately.Thisallowsthe
controllertoinformtheXMBSbypassswitchoftheinternalbyassswitch'spositionwhensignals
aretobetransmittedviaCAN;thisisimportantsothattheXMBSbypassswitchcandetermineifit
isinterlocked(whentheXMBSbypassswitchisininverterstate,buttheinternalbypassswitchis
inbypassstate).
0350058-J0 Rev AL Page 111

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish