Cordex®CXCHPControllerSoftwareManual|13-Cordex®CXPS-HSSHyperboostconvertersystem
13.8.1. Introduction to Matrix C16™ high density connectorized DC distribution
breaker panel
TheMatrixC16™highdensityconnectorizedDCdistributionbreakerpanelprovideshighreliability,high
power,DCdistributioninacompact1RUspacetomaximizerackspaceforsignalequipment.
Traditionaltelecombreakerandfusepanelsuseterminallugsforoutputconnectionsandtherefore
requirespecializedtechnicianstoaddorchangeloads.TheMatrixC16paneluseslockingplug-
inconnectorsofferingasignificantimprovementineaseofuseandcostofinstallation.The1RU
configuration,with400Aofcurrentcapacityand16breakerpositions,offersindustryleadingdensity.
Acceptingsingle-polebreakersratedupto100Aeach,theMatrixC16panelcansupportthemajorityof
networkloadswithinheadends,COs,andhubsites.Theinternalbusworkhasbeenenlarged,adding33
percentmoretotalampacitythanourstandardMatrix300panel.
13.8.2. Matrix C16™ high density connectorized DC distribution breaker panel in a
CXPS-HSS Hyperboost system
Onthecontroller,whenconnectedviaCANbusandacquired,theMatrixC16™highdensity
connectorizedDCdistributionbreakerpanel(device)isseenasamodule(Model:MatrixC16).Ifacquired
appropriately,ausercangototheModules pageoftheuserinterfacetoviewthatmodulewithinthe
CAN Modules table.UsetheGO TO buttontoseetheinformationpresentedbythemodule.
AlthoughMatrixC16moduledatacanbeobservedthroughtheModules pageoftheuserinterface,itcan
alsobeassignedtoaHyperboostsystem.ThebenefitsofassigningamoduletoaHyperboostsystem:1)
datafromallassignedMatrixC16moduleswillbeaggregated,2)alarmingcapabilitiesareavailable,3)
anddatafromthemoduleswillbepresentedontheHyperboostsystempowerflowdiagram.Modulesare
auto-assignedbydefaultbutassignmenttoanotherHyperboostsystemcanbedoneifdesired.
To assign Matrix C16 modules to a system:
1. GotoSystems > Hyperboost System > Inventory > Matrix C16 Modules
2. AnymodulesavailableforassignmentwillappearintheUnassigned Modules table.
Aftermodulesareassigned,aggregateddatacanbeviewedintheDistribution Summary tablefoundat
Systems > Converter System > Status.
Page 144 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish