EasyManuals Logo

EnerSys Alpha Cordex CXC HP User Manual

EnerSys Alpha Cordex CXC HP
279 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #261 background imageLoading...
Page #261 background image
Cordex®CXCHPControllerSoftwareManual|23-Troubleshooting
23.2.7. Rectifier configuration error
Ifthereisaconfigurationerroralarmactive,checktherectifiersettings:
1. GotoSystems > DC System > Inventory > Rectifiers > Configuration.
2. ChecktheOver-Voltage Protection Threshold value.Itmustbesethigherthananysystem
Equalize,Boost,Absorption,orSystemVoltagesettings.Theexactmarginrequireddependson
thetypeofrectifiers,but48voltrectifiersrequiredatleast1volt.
3. CheckthatSystemFloatVoltage,EqualizeVoltage,BoostVoltage,andtheOver-Voltage
ProtectionThresholdaresetwithintherangessupportedbytherectifiersonyoursite.
4. Trysettingrectifierconfigurationtothedefaults.
5. Checktherectifiermanualinformationaboutsettingranges.
6. Saveanychanges.Itmaytakeseveralsecondsforthechangestotakeaffect.
23.2.8. Rediscovering CAN devices
Ifalloftheinstalledequipmentdoesn'tdisplayaftermaintenanceitmaybecausedbydefectiveCAN
buscablesorsequencingofremovalandreplacementofequipmentwiththecontrollerpowereddown
removed.
1. CheckthatallCANbuscablesareinstalledandterminated.
2. PowercycleCANdevicesifpossible.
3. Updatedevicefirmwareifneeded.
23.2.9. Replacing a defective ADIO peripheral
WhenanADIOperipheralfailsorispermanentlyremoved,thesystemgeneratesanalarm.Thealarmis
clearedbyremovingthedevicefromtheinventory.Toremovethedevicefromtheinventory:
1. RemovethedefectiveADIOdevice.
2. InstallthenewADIOdeviceandconnectallthewirestothesameterminals.
3. GotoModules.IntheCAN Modules table,locationtheADIOandselecttheReplace buttonand
followthewizardinstructions.
4. Checkandupdateanyotherconfigurationparameterswhererequired.
23.2.10. Troubleshoot a battery test
CalculationsforSOH,SOC,andRTRBatteryTestalgorithmusedbythecontrolleraredesignedto
workwithleadacidbatterieswhichhaveaPeukertexponentbetween1.0and2.0.Checkyourbattery
manufacturers’specificationstoensurethatthebatteryiswithintheseconstraints.Whenabatteryisnew,
andfullycharged,abatterytestshouldshowthebatterytohave100percentEstimated State of Charge
and100percentormoreEstimated Battery Health.Ifitdoesnot,checkandcorrectthefollowing:
Page 260 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP