6.6. Configure the current transducer
Thesystem,bydefaultdoesnotcontainanycurrenttransducers.Youcanaddorremovecurrent
transducersasneeded.ToconfigureacurrenttransduceryouneedavoltageinputonanADIOmodule.
ToconfigureacurrenttransducerwithanCordex®CXCHPCT-IPMmodule,youneedashuntinputon
anADIOmodule.
To configure a current transducer:
1.
Gotothesystemwhereyouwanttoaddthetransducerandnavigatetotheinventorypage.Goto
Systems > DC System > Inventory > Other Transducers.IntheOther Transducers table,there
willbealistofcurrenttransducersinthesystem.Addorremovethemfromthispage.
YoumaybeusingacurrenttransducerwithInterface & Power Module (IPM).Thisdevicetakes
thevoltagereadingfromacurrenttransduceranddividesthereadingby50.Thefactoredvoltage
readingisthensenttotheCordex®CXCHPL-ADIOperipheralshuntinput.
2. SelecttheGO TO buttonfortheCurrent Transducer youwishtoconfigure.
3. IntheConfiguration table,selectConfigure Current Transducer tolaunchthewizardand
completeeachsteptoconfigurethetransducer.
4. EntertheMeasurement Range inamps.
5. EntertheRange in Volts.
6. SelectCT Current Source.Thiscanbeanyvoltagesource.
7. Optional:entertheOffset calibrationfortheCurrent Transducer ifthereadingerroristoolowor
high.
6.7. Configure the general purpose transducer
Thesystem,bydefaultdoesnotcontainanygeneralpurposetransducers.Youcanaddorremove
generalpurposetransducersasneeded.Toconfigureageneralpurposetransduceryouneedavoltage
inputonanADIOmodule.
To configure a general purpose transducer:
1. Gotothesystemwhereyouwanttoaddthetransducerandnavigatetotheinventorypage.Goto
Systems > DC System > Inventory > Other Transducers.IntheGeneral Purpose Transducers
table,therewillbealistofgeneralpurposetransducersinthesystem.Addorremovethemfrom
thispage.
2. SelecttheGO TO buttonfortheGeneral Purpose Transducer youwanttoconfigure.
3. IntheConfiguration tableassignanameandadescription.
4. SelectTransducer Input Source.Thiscanbeanyvoltagesourceoracustomdata.
5. EntertheTransducer Input Minimum in Volts andTransducer Input Maximum in Volts.
6. EntertheTransducer Output Minimum andTransducer Output Maximum.
Page 102 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish