Cordex®CXCHPControllerSoftwareManual|22-Usingcustomviews,data,timers,counters,scheduler,andcustomactions
Ifpossible,testtheequationtoensureitisprovidingtheexpectedvalue.
22.2.5. Custom data examples
ThefollowingtwoexamplesillustratetheprocessofusingCustom Data forsummingloadshuntcurrents
anddetectingifinteriorairconditioningissettoolowandcreatingaUser Alarm.
22.2.6. Custom data - summing load shunts
Thefollowingexampleshowshowtocreatecustomdatathatsumsupthreeshuntcurrents,andmaps
theresulttothesystemloadinventoryitem.
1. Usethestepsinthedetailedworkflowtocreatecustomdatawhichsumsupthreevariablesto
computeavalueforthetotalloadcurrentinasystem.Whenselectingacurrentreading,itmustbe
selectedfromashuntinthesystem,notattheADIOmoduleinput.
2. TosetuptheLoad tousethisCustom Data,gotoSystems > DC System > Inventory > Loads,
thenselecttheGO TO buttonfortheLoad thatwillrepresentthesumofthethreeshunts.
3. IntheConfiguration table,selecttheEDIT buttontoedittheLoad Current Source entry,and
selecttheCustomData'sResult as Numeric.
4. Whenconfigured,theLoadCurrentSourcewillusethecustomdatacreatedinstep1whichwill
displaythesummedcurrentofthethreeshuntsononeload.
Theloadcurrentnowcorrectlyshowsthesumofthethreeshunts.
22.2.7. Custom data - AC cooling too low user alarm
ThefollowingexampleshowshowtocreateaUser Alarm thatisactiveifitappearsthattheair
conditioningintheroomissettoolow.
1. Usethestepsinthedetailedworkflowtocreatecustomdatathathasanequationwhichevaluates
to“true”iftheoutdoortemperatureisgreaterthan25℃ (77℉), iftheoutdoortemperatureisgreater
thantheindoortemperature,andifthedifferenceisgreaterthan5℃ (41℉).
2. TosetupaUser Alarm tousethisCustom Data,gotoController > Programmability > User
Alarms.
3. SelectAdd Digital User Alarm,andselecttheGO TO buttontoeditthealarmdetails.
4. Configurethealarmname,relayandanyotherinformationrequired.
5. IntheUser Alarm table,selecttheEDIT buttonontheSource line,andthenselecttheCustom
Data createdtodetectifairconditioningissettoolow.
TheUser Alarm activatesiftheindoortemperatureistoolowascomparedtotheoutdoortemperature.
22.3. Using timers
UsingtheTimers featureyoucreatetwotypesoftimers:adelaytimeroranintervaltimer.
Page 244 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish