Cordex®CXCHPControllerSoftwareManual|7-Invertersystems
7.1.3. Phase and group data
Theinvertersystemwillaggregateanddisplaydataabouttheoutputphases,ACinputgroups,andDC
inputgroups.
Theoutputphaseinformationincludesdatasuchastheoutputvoltage,outputpower(inVAandW),
frequency,andloading.
TheACinputgroupinformationincludedatasuchastheinputvoltage,inputpower(VAandW),and
frequencyforeachphase(thereisaone-to-onecorrespondencebetweenthephaseandACinputgroup).
ThenumberofDCinputgroupsisthenumberofredundantDCinputsources.Anexampleisasystem
withseparatebatteries.TheDCinputgroupinformationincludesdatasuchastheDCvoltage,currentand
power(W).
TogetinformationonPhase and Group Data,gotoSystems > Inverter System > Phase and Group
Data.
Notice: When the AC output is light (10 percent or less) or the phases are unbalanced, some of
the data, (percentage of DC input, DC input current or AC output power readings) will tend to be
inaccurate and inconsistent. This is normal. Once the AC output is loaded sufficiently the readings
will be correct.
7.1.4. Live alerts
TheT2SsystemsinaninvertersystemreportalertstatusrelatingtotheT2Ssystemoritsinvertersvia
theLive Alerts table.GotoSystems > Inverter System > Live Alerts.ThetableshowstheOwner of
thealert,thealertType andtheAlert Name.
TheOwner ofthealertindicatesifthealertbelongstotheT2Ssystemortoaspecificinverter.
TheType ofalertindicatesifthealertisanindividualT2Ssystemalert,aninverteralertorasystemalert.
A“system”alertisanalertthatisactiveonallinverters.Asystemalertusuallyindicatesaconfiguration
errororaproblemwithaninputsourceoranoutputwhichisaffectingallinvertersatthesametime.
TheAlert Name displaysthenameofthealertaswellasanumericcode.Thisnumericcodecanbe
usedtocrossreferencethealertintheT2Ssystemlogfilewhentroubleshooting.
AdditionalinformationaboutaspecificalertcanbefoundinAlerts tableoftheOwner identifiedwithinthe
Live Alerts table.
7.1.5. System functions
Theinvertersystemhasthreefunctionsavailable:
ZeroPhaseShift
ACInputPowerLimit
ManualDCPriority
Page 106 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish