Cordex®CXCHPControllerSoftwareManual|7-Invertersystems
7.1.3. Phase and group data
Theinvertersystemwillaggregateanddisplaydataabouttheoutputphases,ACinputgroups,andDC
inputgroups.
Theoutputphaseinformationincludesdatasuchastheoutputvoltage,outputpower(inVAandW),
frequency,andloading.
TheACinputgroupinformationincludedatasuchastheinputvoltage,inputpower(VAandW),and
frequencyforeachphase(thereisaone-to-onecorrespondencebetweenthephaseandACinputgroup).
ThenumberofDCinputgroupsisthenumberofredundantDCinputsources.Anexampleisasystem
withseparatebatteries.TheDCinputgroupinformationincludesdatasuchastheDCvoltage,currentand
power(W).
TogetinformationonPhase and Group Data,gotoSystems > Inverter System > Phase and Group
Data.
Notice: When the AC output is light (10 percent or less) or the phases are unbalanced, some of
the data, (percentage of DC input, DC input current or AC output power readings) will tend to be
inaccurate and inconsistent. This is normal. Once the AC output is loaded sufficiently the readings
will be correct.
7.1.4. Live alerts
TheT2SsystemsinaninvertersystemreportalertstatusrelatingtotheT2Ssystemoritsinvertersvia
theLive Alerts table.GotoSystems > Inverter System > Live Alerts.ThetableshowstheOwner of
thealert,thealertType andtheAlert Name.
TheOwner ofthealertindicatesifthealertbelongstotheT2Ssystemortoaspecificinverter.
TheType ofalertindicatesifthealertisanindividualT2Ssystemalert,aninverteralertorasystemalert.
A“system”alertisanalertthatisactiveonallinverters.Asystemalertusuallyindicatesaconfiguration
errororaproblemwithaninputsourceoranoutputwhichisaffectingallinvertersatthesametime.
TheAlert Name displaysthenameofthealertaswellasanumericcode.Thisnumericcodecanbe
usedtocrossreferencethealertintheT2Ssystemlogfilewhentroubleshooting.
AdditionalinformationaboutaspecificalertcanbefoundinAlerts tableoftheOwner identifiedwithinthe
Live Alerts table.
7.1.5. System functions
Theinvertersystemhasthreefunctionsavailable:
•
ZeroPhaseShift
• ACInputPowerLimit
• ManualDCPriority
Page 106 0350058-J0 Rev AL