Cordex®CXCHPControllerSoftwareManual|20-Maintainingthecontroller
To share which published data or which published systems should be shared with other
controllers:
1.
GotoController > Communication > Data Sharing > Published Data and Systems.
Published Data: SelecttheEDIT buttonnexttooneofthepublishedvalues.
Selectthedatapointtobesharedwithothercontrollers,thenselectSave.
Published Systems: SelecttheEDIT buttonnexttooneofthepublishedvalues
Selectthesystemtobesharedwithothercontrollers,thenselectSave.
2. Thisprocesscanberepeatedtosharemultipledatapointsorsystemswithothercontrollers.
Afterperformingtheaboveprocedure,othercontrollerswillbeabletosubscribetothiscontrollerto
receivedatafromit.
20.3.11.2. Data subscriptions
Data Subscriptions areawayforuserstoreadandusePublished Data and Systems fromother
controllers.
ToconfigureaData Subscription:
1. GotoController > Communication > Data Sharing > Data Subscriptions.
2. SelectAdd Data Subscription.
3. SelecttheGO TO buttonofthisnewlycreatedData Subscription.
4. SelecttheEDIT buttonbesideIP Address,enterintheIPaddress(DNSnameoranIPv4/IPv6
address)ofthecontrollertoreaddatafrom,thenselectSave.
Afterconfiguration,theData Subscription willstartreadinganyconfiguredPublished Data and
Systems fromtheremotecontroller.Datawillbereadandupdatedeverytenseconds.
Ifthereareanyproblemscommunicatingwiththeremotecontroller,thosewillbeindicatedin
Communication Status,potentiallybeingraisedasanalarmthroughtheCommunication Error alarm.
Somecommonerrorscouldbe:
IPaddressconfiguredincorrectly.
Thecontrollerortheremotecontrollerarenotconnectedtoanynetwork,notconnectedtothe
samenetwork,ornotpubliclyvisible.
Nopublisheddataconfiguredontheremotecontroller(thiswillbeindicatedasaNo Published
Data status).
20.3.12. Maintenance mode
Asofcontrollersoftwareversion7.40,afeaturecalledMaintenance Mode isavailableonthe
controller.Thisfeatureisintendedforuserswhowanttocommunicatetootherusersthatthecontroller
Page 190 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish