Cordex®CXCHPControllerSoftwareManual|5-DCpowersystems
To configure temperature compensation:
1. GotoSystems > DC System > System Functions > Temperature Compensation.Notethat
youmusthaveabatterydefinedintheDCSysteminordertohavethismenuitemavailableunder
System Functions.
2. Enable/disableTemp Comp in Float,Temp Comp in Equalize andTemp Comp in Absorption
3. SettheSlope basedonthebatterymanufacturer’sinformation.
4. SettheUpper Temperature Breakpoint Voltage toavaluebelowthefloatvoltage.
5. SettheLower Temperature Breakpoint Voltage toavalueabovethefloatvoltage.
6. AdjustthevaluesandenableordisabletheTemp Comp Sensor Fail andTemp Comp Voltage
Warning alarms.
5.3.16. Configure battery runtime and health estimation
TheBatteryRuntimeandHealthEstimationisusedtocalculateEstimated State of Charge during
chargesanddischarges,Estimated Battery Health fordischargesthatexceeda20percentdepthof
discharge(DOD)andEstimated Battery Runtime atalltimes.
To configure battery runtime and health estimation:
1. GotoSystems > DC System > System Functions > Battery Runtime & Health Estimation.
NotethatyoumusthaveabatterydefinedintheDCSysteminordertohavethismenuitem
availableunderSystem Functions.
2. IntheConfiguration table,selecttheEDIT buttontoenableordisableBattery Estimation.
3.
SettheLoad Model.TheloadmodelhasnoaffectoncalculatingEstimated State of Charge or
Estimated Battery Health butithasasignificantimpactoncalculatingtheEstimated Battery
Runtime.
a. Withtheconstantcurrentmodel,theloadcurrentisexpectedtostaythesameastheload
voltagedecreases.
b. Withtheresistivemodel,theloadcurrentisexpectedtodecreaseastheloadvoltage
decreases.
c. Withtheconstantpowermodel,theloadcurrentisexpectedtoincreaseastheloadvoltage
decreases.
4. SettheBattery LVD.IfthereisnoBLVD,thiscanbeleftunknown.
5.3.17. Run a manual battery test
OnceyourDCSystemissetup,runningamanualbatterytestmaybeassimpleaspressingtheStart
Manual Battery Test command.
Page 94 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish