Cordex®CXCHPControllerSoftwareManual|5-DCpowersystems
Logic:Selectalogicaloperation:greaterthan,lessthan,isTrueandisFalse
Limit:Whenusinggreaterthanorlessthan,setanumbertocompareValue to Test
against.
Ensurethatanyoptionaldisconnectconditionscannotbetrueasthesametimeasanyoptional
reconnectconditions,otherwisethedisconnectmaygetstuckineitherthedisconnectedor
reconnectedstate.
5.3.10.1. Configure a battery disconnect with latching contactor
To configure a battery disconnect with latching contactor:
1. GotoSystems > DC System > Inventory > Disconnects .
2. IntheDisconnects table,selecttheCreate Disconnect buttontolaunchthewizard.
3. AttheSelect Disconnect Type step,selectBattery Disconnect with Latching Contactor and
selecttheNext buttontoexitthewizard.
4. AnewlycreatedDisconnect willbedisplayedintheDisconnects table.
5.
SelecttheGO TO buttonnexttothenewlycreateddisconnect.IntheConfiguration table,forthe
disconnect,configurethefollowing:
a. Enable:Thiswillenablethedisconnect.
b. Relay to Close:Thisistherelaythatwillbeusedtoclosethelatchingcontactor.Usingthe
selector,setthisrelaytotheADIOmodulerelaywhichcorrespondstotherelayinputofthe
latchingcontactorinterfacewhichwillclosethelatchingcontactor.
c. Relay to Open:Thisistherelaythatwillbeusedtoopenthelatchingcontactor.Usingthe
selector,settherelaytotheADIOmodulerelaywhichcorrespondstotherelayinputofthe
latchingcontactorinterfacewhichwillopenthelatchingcontactor.
d. Contactor State Source:Thisisthedigitalinputthatiswiredtosensethecontactorstate.
Usingtheselector,setthesourcetothedigitalinputwhichcorrespondstotheauxiliaryinput
ofthelatchingcontactorinterface.Forproperoperationofabatterydisconnectwithlatching
contactor,thissourceisrequiredtobeconfigured.
6.
IntheDisconnect On Voltage table,configurethefollowing:
a. Voltage Disconnect Threshold:Thisisthevoltageatwhichthedisconnectwillactivate
andopentheconnection.Thisthresholdcannotbedisabled.
b. Voltage Connect Threshold:Thisisthevoltageatwhichthedisconnectwillde-activate
andreconnect.Thisthresholdcannotbedisabled.
5.3.11. Configure lead acid or NiCad battery parameters
Thesystemisonlypermittedtohaveasinglebattery.Thebatterymayconsistofmultiplebatterystrings.
WhentheDCSystemisbeingcreatedusingtheDCsystemcreationwizard,theuserwillbegiventhe
optionofaddingabatterytothesystem,ornot.
If a battery is required, configure battery parameters:
0350058-J0 Rev AL Page 87

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish