Cordex®CXCHPControllerSoftwareManual|13-Cordex®CXPS-HSSHyperboostconvertersystem
TheHyperboostsystemcreatedwillhaveareasonablesetofdefaultsandassociatedalarms.Optional
converteritems,suchasName,Description,SystemNumber,andSerialNumber,canbeusedto
describeandorganizeyoursystem.
NewlydiscoveredconvertersareautomaticallyassignedtotheHyperboostsystem.Howeverifthereis
morethanoneHyperboostsystem,convertersaregroupedintoUnassigned Modules,andthenyoucan
addthemtothesystemmanually.
Youcanconfiguretheconverteralarmsassociatedwiththesystem.Youcanenableordisablethe
alarms,changethepriority,maprelaystothealarms,andwhereapplicable,modifythethresholds.
To create a converter system:
1. GotoSystems > Add or Remove Systems.
2. SelectCreate Converter System.Namethesystemifrequired.
3. FromtheSelect System Type dropdownlist.SelectHyperboost System 48V-58V
4. Stepthroughtherestofthewizardinstructions.
5. LaunchtheConfigure Hyperboost System wizardtoconfigurethebasicsystemsettingsandthe
systeminventory.
13.3. Configure the CXPS-HSS Hyperboost converters
Thesesettingsincludestartdelay,outputvoltage,orover-voltageprotectionthreshold.
Notice: The load bus output voltage is also the voltage that the converters default to if they lose
communication with the controller. The converters will drop any of the adjustments made by the
controller to perform load sharing and just try to meet the configured output voltage.
Thisfeaturehasatimedelaythatvariesaccordingtoconverters.Mostconvertersreverttooutputmode
afterfiveminutes.Checktheconvertermanualforalistofdefaultparameters.
To configure the converters:
1. GotoSystems > Hyperboost System > Inventory > Converters > Configuration.
2. IntheConfiguration table,setupyourconvertergroupconfigurationsettings.Theseinclude,
Load Bus Output Voltage andLoad Bus Over-voltage Protection Limit threshold.
3. Configurethesettingsfortheconverters.Thevaluesforthesesettingsdependonyourspecific
system.
13.4. Configure the shunts
Bydefaultthesystemhasnoshunts.Youmayaddorremoveshuntsasneeded.
ToconfigureashuntyouneedanADIOmodulewithcurrentinputs.Theshuntwillmapthecurrentinputs
fromtheADIOmoduletotheLoad Current Source fieldoftheLoad configurationtableortheBattery
Current Source fieldoftheBattery Configuration table.
0350058-J0 Rev AL Page 141