Cordex®CXCHPControllerSoftwareManual|4-Gettingstarted
Notice: The message presented is not the entire message displayed and the timestamp is
formatted via rSyslog on Linux. It is to be used as a reference for the information detailed below.
UsingtheSyslogmessageformat,thecontrollerwillcurateamessagewiththefollowing:
1. InSyslogmessageformat,theAppNameistheCXCHP[Version].
2. InSyslogmessageformat,theMsgIdarethespecifictypesofeventsgeneratedbythecontroller.
Theseeventscategoriesare:ConfigurationEvent,ControllerEvent,AlarmEvent,andModuleEvent.
Tofindthesegeneratedeventsonthecontrollerwebinterface,gotoLogs > Events & Alerts.
a. AConfigurationEvent canbegeneratedwhenconfigurationonthecontrollerchanges.
b. AControllerEvent canbegeneratedwhenanyaction,statetransitions,oranyeventthat
doesnotfallintotheotherthreecategories.
c. AnAlarmEvent canbegeneratedwhenanyalarmisactivatedordeactivated.
d. AModuleEvent canbegeneratediftransitionsoccuronamodule.
3. AlleventtypeswillalwayshaveaseveritylevelofInformationbesidesAlarmEvent.
4. AnAlarmEvent hasaseveritylevelthatcanchange.Thischangeisbasedonthespecificalarms
priorityconfigurationonthecontroller.Thealarmprioritiesonthecontrolleraremappedtothe
severitiesofSyslog.Themappingscanbefoundinthefollowingtable.
5. IntheSyslogmessageformat,thecontrollereventmessagewillhavetheformatof"[Source]:
SourceoftheEvent,[Name]:NameoftheEvent,[Value]:ValueoftheEvent".
Table 4-4 ControlleralarmprioritiestoSyslogseveritiesmappingtable
Controller priority level Syslog severity level (name) Syslog severity level (#)
Critical Critical 2
Major Error 3
Minor Warning 4
Warning Notice 5
0350058-J0 Rev AL Page 65