EasyManua.ls Logo

EnerSys Alpha Cordex CXC HP - Battery Test

EnerSys Alpha Cordex CXC HP
279 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cordex®CXCHPControllerSoftwareManual|5-DCpowersystems
Alarm willtriggerindicatingthepositionofthecontactorisnotinitsexpectedstate.Ifthissourceisnot
set,thecontrollerwillnotattempttocloseoropenthecontactorasthestateisunknown.
Contactor retry countdown
TheContactor Retry Countdown isfoundintheStatus table.Thecontactorretrycountdownwill
automaticallystartcountingdownafterthreeretries.Aftertheretrycountdownreaches0,thecontroller
willautomaticallyattempttoretryclosingoropeningthecontactorthreetimes.Iftheexpectedstateisnot
reached,thecontactorretrycountdownwillstartover.
Test disconnect open button
Totestthecontactor,thereisaTest Disconnect Open buttonlocatedintheStatus table.Atestcanonly
beinitiatedifthedisconnectState,foundintheStatus table,isInactive (contactorclosed).
TheTest Disconnect Open buttonwillopenthecontactor.Thecontactorwillremainopenfor60
seconds,thencloseautomatically.
5.2.7. Battery test
AbatterytestisusedtoupdatetheEstimated Battery Health ofaleadacidbattery.Thesettingsfor
thisfeaturecanbefoundintheSystems > DC System > System Functions > Battery Test menu.
TheEstimated Battery Health willbeupdatedontheSystems > DC System > System Functions >
Battery Runtime & Health page.
Definitions
Battery test termination voltage: Thevoltagethresholdatwhichthetestnormallyends.
Battery test timeout: Themaximumtimethetestcanrunbeforeitisstopped.
Battery test termination on SOC: EnableordisabletheBatteryTestTerminationSOCthreshold
toterminateabatterytest.
Battery test termination SOC: TheStateofCharge(SOC)thresholdatwhichthetestnormally
ends.
Battery test alarm: Thebatterytestisactive.
Using the test discharge (TD) mode
Ifthetestisstartedwhenthebatteryisfullycharged,theresultsofthebatterycapacityestimate
willbemoreaccurate.Usechargecurrentcontroltolimitthebatteryrechargecurrenttothebattery
manufacturersspecifiedmaximumvalue.
Duringatest,theEstimated State of Charge andEstimated Battery Runtime hourscanbeviewedvia
theSystems > DC System > Status menuintheBattery tableortheSystems > DC System > System
Functions > Battery Runtime & Health menuintheStatus table.
Page 74 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP