Cordex®CXCHPControllerSoftwareManual|5-DCpowersystems
Alarm willtriggerindicatingthepositionofthecontactorisnotinitsexpectedstate.Ifthissourceisnot
set,thecontrollerwillnotattempttocloseoropenthecontactorasthestateisunknown.
Contactor retry countdown
TheContactor Retry Countdown isfoundintheStatus table.Thecontactorretrycountdownwill
automaticallystartcountingdownafterthreeretries.Aftertheretrycountdownreaches0,thecontroller
willautomaticallyattempttoretryclosingoropeningthecontactorthreetimes.Iftheexpectedstateisnot
reached,thecontactorretrycountdownwillstartover.
Test disconnect open button
Totestthecontactor,thereisaTest Disconnect Open buttonlocatedintheStatus table.Atestcanonly
beinitiatedifthedisconnectState,foundintheStatus table,isInactive (contactorclosed).
TheTest Disconnect Open buttonwillopenthecontactor.Thecontactorwillremainopenfor60
seconds,thencloseautomatically.
5.2.7. Battery test
AbatterytestisusedtoupdatetheEstimated Battery Health ofaleadacidbattery.Thesettingsfor
thisfeaturecanbefoundintheSystems > DC System > System Functions > Battery Test menu.
TheEstimated Battery Health willbeupdatedontheSystems > DC System > System Functions >
Battery Runtime & Health page.
Definitions
Battery test termination voltage: Thevoltagethresholdatwhichthetestnormallyends.
Battery test timeout: Themaximumtimethetestcanrunbeforeitisstopped.
Battery test termination on SOC: EnableordisabletheBatteryTestTerminationSOCthreshold
toterminateabatterytest.
Battery test termination SOC: TheStateofCharge(SOC)thresholdatwhichthetestnormally
ends.
Battery test alarm: Thebatterytestisactive.
Using the test discharge (TD) mode
Ifthetestisstartedwhenthebatteryisfullycharged,theresultsofthebatterycapacityestimate
willbemoreaccurate.Usechargecurrentcontroltolimitthebatteryrechargecurrenttothebattery
manufacturersspecifiedmaximumvalue.
Duringatest,theEstimated State of Charge andEstimated Battery Runtime hourscanbeviewedvia
theSystems > DC System > Status menuintheBattery tableortheSystems > DC System > System
Functions > Battery Runtime & Health menuintheStatus table.
Page 74 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish