Cordex®CXCHPControllerSoftwareManual|24-Cordex®CXCHPcontrollerreferenceguide
Table 24-1 SupportforCANmodules(continued)
Category Device name Controller software support
Converter Cordex®CXPS-HSSHyperboostConverter
System
Version8.00
ADIO MatrixC16™HighDensityConnectorizedDC
DistributionBreakerPanel
Version8.00
24.2. Communication ports
Therearethreesetsofportsthatareusedforcontrollercommunication:
TwoEthernetports,commonlyreferredtoasthefrontandrearEthernetports.
TwoUSBports,commonlyreferredtoasthefrontandrearUSBports.
TwoCANports,commonlyreferredtoasCAN1andCAN2.
24.2.1. Ethernet ports
TheEthernetportssupportastandardRJ45connectionandcanrunat10BASE-Tor100BASE-Tspeeds
withautoMDI-Xdetection(MediumDependentInterfacecrossoverdetection)toeliminatetheneedfor
cross-overcables.
TheEthernetportssupporttheIPv4andIPv6protocols.TheIPv4protocolsupportsbothstaticIPand
DHCPconfiguration.TheIPv6protocolwillconfigurealink-localaddressautomatically.Addresseswith
otherscopesareconfiguredbyRouterAdvertisements(RA).BoththeLCDandwebinterfacewilldisplay
thefulllistofIPv6addressesthathavebeenconfiguredforeachport.
YoucanalsouseIPv6addressesforoutgoingmessagesincludingemailserversandSNMPdestinations.
SNTPdoesnotsupportIPv6atthistime.
ThecontrollerdoesnotregisteritselfwithDNSserversnorcanitbeconfiguredtojoinadomainorwork
group.However,thecontrolleriscapableofusingaDNSservertoresolvedomainnamesifthegateway
issetuptoallowthat.
Notice: While there are two Ethernet ports available on the controller, it is recommended that
they are not both connected to the same network. There is a concern that network management
systems and higher level control systems will see the controller as two devices and get duplicate
notifications (SNMP traps for example) for a single device.
24.2.2. USB ports
TheUSBportssupportastandard,full-sizeUSBhostconnection.
0350058-J0 Rev AL Page 271

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP