Cordex®CXCHPControllerSoftwareManual|22-Usingcustomviews,data,timers,counters,scheduler,andcustomactions
AChange Relay Action hasfourconfigurationfields:
Name: Theeditablenameforthisitem.
Description: Additionalinformationtodescribethisitem.
Relay To Change: Therelaythatwillbechangingbasedonthespecifiedcondition.
Condition: Abooleanfieldthatwillcontroltherelay.
Therearealsofieldsthatdescribethestateoftheaction:
Field Value When Condition True: WhatstatetherelaywillbeinwhenCondition Value istrue.
Field Value When Condition False Or ---: WhatstatetherelaywillbeinwhenCondition Value is
falseorunknown.
Condition Value: ThepresentvalueofCondition.
Field Value: ThepresentvalueofRelay To Change.
Change relay action operation
TheChange Relay actionoperatesasfollows:
WhentheCondition Value isfalseorunknown,therelaywillbeinitsnormalstate.
WhentheCondition Value istrue,therelaywillbeinitsabnormalstate.
22.9.2. Configure a change field to constant action
TheChange Field To Constant Action featurecanbeusedtochangethevalueofafieldbasedon
specificsituations.Thiscanbeusefultocontrolthestateofthesystembasedonexternalconditions.For
example,whenageneratorison,thesystemcanbesettochargethebatteriesatalowerratesothatit
doesnotdrainthegenerator.
ToaccessthisfeaturegotoController > Programmability > Custom Data.
AChange Field To Constant actionhassixconfigurationfields:
Name: Theeditalenameofthisitem.
Description: Additionalinformationtodescribethisitem.
Field To Change: Thefieldthatwillbechangingbasedonthespecifiedcondition.
Condition: AbooleanfieldthatwillcauseField To Change tochangetodifferentvalues.
Field Value When Condition True: ThevalueofField To Change whenCondition Value istrue.
Field Value When Condition False Or ---: ThevalueofField To Change whenCondition Value
isfalseorunknown.
Therearealsofieldsthatdescribethestateoftheaction:
Page 252 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish