Cordex®CXCHPControllerSoftwareManual|5-DCpowersystems
5.3.3. Configure basic DC system settings
TheConfigure System pagehasthreetables(Configuration,System Properties,andAlarms)with
somebasicsettingsthatmustbeconfigured.
To configure basic DC system settings (from the main dashboard):
1. GotoSystems > DC System > Configure System.
2.
IntheConfiguration table:
a. Setthesystemname,description,number,andserialnumber.
b. Setthefloatvoltagesetting.Thisisthedesiredoutputvoltageoftherectifierswhenthe
systemisinfloatmode.
c. Setthesystemvoltagesource,whichisthevoltageusedtocontrolthesystem.Thisisthe
inputoftheADIOmodulethatmeasuressystemoutputvoltage,andisusuallythesame
inputasthebatteryvoltage.
3. IntheAlarms table,configuretherelatedalarms.
5.3.4. Configure dynamic thresholds for output voltage alarms
BoththeHighandLowOutputVoltagealarmscanuseadynamicallyadjustedthreshold.ThisAdjusted
LimitiscalculatedbyaddingthedifferencebetweentheVoltageRegulationSetpointandtheFloat
VoltagetotheconfiguredLimit.TousedynamicallyadjustedthresholdsforanOutput voltage alarm:
1. GotoSystems > DC System > Configure System.
2. IntheAlarms table,selecttheGO TO buttonfortheOutput Voltage alarmtoconfigure.
3. UsethedropdownmenutosettheAbsoluteorAdjustedfieldtoAdjusted.
5.3.5. Configure the rectifiers
Thesearesettingsthatincludestartdelay,safemodevoltage,orover-voltageprotectionthreshold.
Notice: The Safe Voltage is the voltage that the rectifiers default to if they lose communication
with the controller. This feature has a time delay that varies according to rectifier. Most rectifiers
revert to Safe Mode after five minutes. Check the rectifier manual for a list of the default
parameters.
RectifieroutputvoltageisconfiguredfromtheSystems > DC System > Configure System menu.
To configure the rectifiers:
1. GotoSystems > DC System > Inventory > Rectifiers > Configuration.
2. Setupyourrectifiergroupconfigurationsettings.Theseinclude,startdelay,safemodevoltage,or
overvoltageprotectionthreshold.
Youcanconfigurethegroupsettings,usinginformationinthefollowingtable.
Page 82 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish