Cordex®CXCHPControllerSoftwareManual|22-Usingcustomviews,data,timers,counters,scheduler,andcustomactions
Trigger: Thevalueofthetimertrigger.Whenthisvaluegoesfromfalsetotrue,thedelaytimer
startsandtheoutputgoestrueaslongastheReset valueisfalse.
Reset: Thevalueofthetimerreset.Whenthisvalueistrue,thetimeroutputwillbefalse.
TheReinitialize Timer buttoncanbeusedifthetimerconfigurationhasbeenchangedwhilethetimeris
active.
Notice: It is also possible to test the timer or force it into a desired state using the Force Timer to
Start and Force Timer to End buttons, even if Start Event has not been configured.
Force Timer to Start simulatestheStart Event goingfromfalsetotrue.
Force Timer to End setstheDelay Time Remaining goingtozeroandthetimergoingintoits
terminalstate.
Delay timer operation
TheDelay Timer operatesasfollows:
WhentheReset istrue,orifAuto Reset isenabledandthetimertriggersourceisfalse,thetimer
outputisalwaysfalseandtheDelay Time Remaining issettotheinitialvalue.
WhenOutput True When valueisWhen Running andtheTrigger inputgoesfromfalsetotrue,
theOutput goestrueandtheDelay Time Remaining startscountingdownfromthedelayvalue.
WhenOutput True When valueisWhen Delay Over andtheTrigger inputgoesfromfalseto
true,theDelay Time Remaining beginscountingdownandwhenitreaches0,theOutput goes
true.
Ifthetimerisactivelycountingdownseconds,andtheOutput istruewhentheTrigger inputgoes
fromfalsetotrue,thetimerstartscountingdownsecondsstartingfromtheconfigureddelaytime
foraslongastheRetrigger isenabled.
WhentheReinitialize Button ispressed,thetimerOutput willbesetfalseandtheDelay Time
Remaining issettotheinitialvalue.
22.3.2. Configure the interval timer
Anintervaltimerhasfourconfigurationfields:
Name: Theeditablenameforthisitem.
Description: Additionalinformationtodescribetheitem.
Start Event Source: ThefieldthatrepresentsthetimerStart Event.Itisusuallysettotheresultof
acustomdata.
Stop Event Source: ThefieldthatrepresentsthetimerStop Event.Itisusuallysettotheresultof
acustomdata.
Page 246 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish