Cordex®CXCHPControllerSoftwareManual|22-Usingcustomviews,data,timers,counters,scheduler,andcustomactions
Trigger: Thevalueofthetimertrigger.Whenthisvaluegoesfromfalsetotrue,thedelaytimer
startsandtheoutputgoestrueaslongastheReset valueisfalse.
Reset: Thevalueofthetimerreset.Whenthisvalueistrue,thetimeroutputwillbefalse.
TheReinitialize Timer buttoncanbeusedifthetimerconfigurationhasbeenchangedwhilethetimeris
active.
Notice: It is also possible to test the timer or force it into a desired state using the Force Timer to
Start and Force Timer to End buttons, even if Start Event has not been configured.
Force Timer to Start simulatestheStart Event goingfromfalsetotrue.
Force Timer to End setstheDelay Time Remaining goingtozeroandthetimergoingintoits
terminalstate.
Delay timer operation
TheDelay Timer operatesasfollows:
WhentheReset istrue,orifAuto Reset isenabledandthetimertriggersourceisfalse,thetimer
outputisalwaysfalseandtheDelay Time Remaining issettotheinitialvalue.
WhenOutput True When valueisWhen Running andtheTrigger inputgoesfromfalsetotrue,
theOutput goestrueandtheDelay Time Remaining startscountingdownfromthedelayvalue.
WhenOutput True When valueisWhen Delay Over andtheTrigger inputgoesfromfalseto
true,theDelay Time Remaining beginscountingdownandwhenitreaches0,theOutput goes
true.
Ifthetimerisactivelycountingdownseconds,andtheOutput istruewhentheTrigger inputgoes
fromfalsetotrue,thetimerstartscountingdownsecondsstartingfromtheconfigureddelaytime
foraslongastheRetrigger isenabled.
WhentheReinitialize Button ispressed,thetimerOutput willbesetfalseandtheDelay Time
Remaining issettotheinitialvalue.
22.3.2. Configure the interval timer
Anintervaltimerhasfourconfigurationfields:
Name: Theeditablenameforthisitem.
Description: Additionalinformationtodescribetheitem.
Start Event Source: ThefieldthatrepresentsthetimerStart Event.Itisusuallysettotheresultof
acustomdata.
Stop Event Source: ThefieldthatrepresentsthetimerStop Event.Itisusuallysettotheresultof
acustomdata.
Page 246 0350058-J0 Rev AL