Cordex®CXCHPControllerSoftwareManual|14-Generator
• Generator Running too Long: Ifthisalarmisactive,thenthegeneratorhasrunlongerthanthe
thresholdconfiguredinthealarm'sdetailspage.Thegeneratorisstillrunningbecauseeitherthe
generator'sCall to Stop isnotTrue,orithasnotexceededitsconfiguredMinimum Runtime.
• Generator Status Mismatch: TheGenerator Status Signal isdetectingthatthestatusofthe
generatordoesnotmatchwhatisexpected.EitherthegeneratorisrunningwhentheGenerator
Status indicatesitshouldnotbe,orelseitisnotrunningwhenitshouldbe.Thisalarmdoesnot
activateuntilapproximately30secondsafterthemismatchisfirstmeasured,toallowtimeforthe
generatortostartuporshutdown.
14.8. Legacy generator
ALegacy Generator isaspecializedtypeofACsourceorDCsourcewhichallowsageneratorto
bestartedandstoppedwitharelay.Thelegacygeneratorhasbeensucceededbythegenerator,as
describedintheprevioussection.
Thestandardconditiononwhichtostartorstopageneratorisbasedonavoltage.Thecontrollerallows
theusertochooseanyvoltageinthesystemandsetitastheVoltage to Monitor,withastartthreshold
andastopthreshold.ThegeneratorwillbestartediftheVoltage to Monitor fallsbelowtheStart Voltage
Threshold,andwillbestoppediftheVoltage to Monitor climbsabovetheStop Voltage Threshold.
Theoptionalstartorstopconditionscanbeusedtostartandstopthegeneratorbasedonothertypesof
conditions.Forexample,thebatterySOCcouldbeused.TheabilitytouseCustomDataorothersystem
valuesgivesthegeneratorcontrolalotofflexibility;however,caremustbetakentoensurethatthestart
andstopconditionsmakesense.Otherwise,itispossiblefortheusertocreate,forexample,astart
conditionthatisalwaystrue,inwhichcasethegeneratorwouldnotstoprunning.
TheMinimumRuntimeassuresthatthegeneratorwillnotbestartedtoonlyrunfortooshortaperiod
oftime.Oncethegeneratorhasstarted,itwillcontinuetorunfortheMinimumRuntimeevenifastop
conditionhasbecometrue.
TheMaximumRuntimeisintendedtoensurethatthegeneratordoesnotcontinuetorunindefinitelyeven
ifnostopconditioncomestrue.AfterrunningfortheMaximumRuntime,thegeneratorwillattempttoshut
down.Itshouldbenotedthatifastartconditionisstilltrue,itwouldstartupagainimmediately.Inthat
case,aneventmessagewillbelogged.Additionally,thereisaGenerator Running Too Long alarmthat
maybeenabledtohelpalerttheusertothissituation.
14.8.1. Create a legacy AC generator
To create a legacy AC generator:
1. IfanACsourcesystemdoesnotalreadyexist,createitbygoingtoSystems > Add or Remove
Systems andlaunchtheCreate System wizard.
2. GotoSystems > AC Source System > Inventory.
3. IntheAC Sources table,selectAdd AC Source buttontolaunchthewizard.
4. SettheName andthenselectNext.
5. SelectLegacy Generator fromtheAC Source Type dropdownlist.SelectNext.
0350058-J0 Rev AL Page 153