Cordex®CXCHPControllerSoftwareManual|14-Generator
Generator Running too Long: Ifthisalarmisactive,thenthegeneratorhasrunlongerthanthe
thresholdconfiguredinthealarm'sdetailspage.Thegeneratorisstillrunningbecauseeitherthe
generator'sCall to Stop isnotTrue,orithasnotexceededitsconfiguredMinimum Runtime.
Generator Status Mismatch: TheGenerator Status Signal isdetectingthatthestatusofthe
generatordoesnotmatchwhatisexpected.EitherthegeneratorisrunningwhentheGenerator
Status indicatesitshouldnotbe,orelseitisnotrunningwhenitshouldbe.Thisalarmdoesnot
activateuntilapproximately30secondsafterthemismatchisfirstmeasured,toallowtimeforthe
generatortostartuporshutdown.
14.8. Legacy generator
ALegacy Generator isaspecializedtypeofACsourceorDCsourcewhichallowsageneratorto
bestartedandstoppedwitharelay.Thelegacygeneratorhasbeensucceededbythegenerator,as
describedintheprevioussection.
Thestandardconditiononwhichtostartorstopageneratorisbasedonavoltage.Thecontrollerallows
theusertochooseanyvoltageinthesystemandsetitastheVoltage to Monitor,withastartthreshold
andastopthreshold.ThegeneratorwillbestartediftheVoltage to Monitor fallsbelowtheStart Voltage
Threshold,andwillbestoppediftheVoltage to Monitor climbsabovetheStop Voltage Threshold.
Theoptionalstartorstopconditionscanbeusedtostartandstopthegeneratorbasedonothertypesof
conditions.Forexample,thebatterySOCcouldbeused.TheabilitytouseCustomDataorothersystem
valuesgivesthegeneratorcontrolalotofflexibility;however,caremustbetakentoensurethatthestart
andstopconditionsmakesense.Otherwise,itispossiblefortheusertocreate,forexample,astart
conditionthatisalwaystrue,inwhichcasethegeneratorwouldnotstoprunning.
TheMinimumRuntimeassuresthatthegeneratorwillnotbestartedtoonlyrunfortooshortaperiod
oftime.Oncethegeneratorhasstarted,itwillcontinuetorunfortheMinimumRuntimeevenifastop
conditionhasbecometrue.
TheMaximumRuntimeisintendedtoensurethatthegeneratordoesnotcontinuetorunindefinitelyeven
ifnostopconditioncomestrue.AfterrunningfortheMaximumRuntime,thegeneratorwillattempttoshut
down.Itshouldbenotedthatifastartconditionisstilltrue,itwouldstartupagainimmediately.Inthat
case,aneventmessagewillbelogged.Additionally,thereisaGenerator Running Too Long alarmthat
maybeenabledtohelpalerttheusertothissituation.
14.8.1. Create a legacy AC generator
To create a legacy AC generator:
1. IfanACsourcesystemdoesnotalreadyexist,createitbygoingtoSystems > Add or Remove
Systems andlaunchtheCreate System wizard.
2. GotoSystems > AC Source System > Inventory.
3. IntheAC Sources table,selectAdd AC Source buttontolaunchthewizard.
4. SettheName andthenselectNext.
5. SelectLegacy Generator fromtheAC Source Type dropdownlist.SelectNext.
0350058-J0 Rev AL Page 153

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish