Cordex®CXCHPControllerSoftwareManual|23-Troubleshooting
ItisrecommendedtousetheComms Lost Action settingontheRelay Details page.Ifcommunication
islostbetweentheinternalcontrollerandtheFXMADIOmodule,therelaywillde-energizefiveminutes
aftercommunicationislost.
Thisfeatureisavailableinversion6.10andlater.TheCANmodulefirmwarealsoneedstobeupdatedto
aversionthatsupportsthisfeature.
23.2. Troubleshoot a rectifier system
Thissectioncoverspossibleissuesandfixesforyoursystem.Alsoseethereadmenotesthatshipwith
thecontrollersoftware.
23.2.1. Relays not triggered during alarm conditions
If the relays are not trigged during alarm conditions try the following:
Ensurealarmconditionismappedtoarelay(Alarms > All Alarm Settings).
Ensurepolarityoftherelayissetcorrectly
EnsureCutoffAllAlarmshadnotbeenselected
EnsureADIOiscommunicating
23.2.2. Rectifier alarms and alerts
Alarm:Analarmisanotificationofachangetothestateofthecontroller.Alarmscanbeconfiguredwith
thresholds(ifapplicable),mappedtorelaysandwilltriggerSNMPnotifications.
Alert:Analertisanotificationfromadevicethatindicatesaproblemorchangeinstate.Analertisnot
configurable.Thestatusofanalertisviewablefromadevice'sdetailedstatuspage.Forexample,toview
rectifieralertsgotoSystems > DC System > Inventory > Rectifiers > Status,andselecttheGO TO
button.
Rectifier Minor Alert:Indicatesapotentialminorproblemthatdoesn'tposeanimmediaterisktothe
rectifier'sabilitytooutputpower.
Rectifier Fail Alert:Indicatesaproblemwiththerectifier'sabilitytooutputpower.
IfthesystemhasanactiveRectifier Minor orRectifier Fail alarm,youcanfindoutthesourceandcause
ofthealarmasfollows:
1. GotoSystems > DC System > Inventory > Rectifiers > Status andlookatthe# Alerts column.
2. LookforarectifierinthelistwithmorethanzeroalertsandselecttheGO TO button.Thepage
displaysaRectifier Alerts tablelistingallpossiblerectifiersalerts.
3. Sortthetabletofindtheactivealerts.SelecttheGO TO buttonforadescriptionofthealert.This
informationallowsyoutotroubleshoottheproblem.
0350058-J0 Rev AL Page 257

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish