Cordex®CXCHPControllerSoftwareManual|24-Cordex®CXCHPcontrollerreferenceguide
24.3.5. 220 volt system default values and ranges
Thistableprovidesthedefaultvaluesandrangesfora220voltsystem.
Table 24-6 220voltsystemdefaultvaluesandranges
Setting name Default Minimum Maximum
AllowedVoltageRange N/A 180 320
FloatVoltage 247.5 180 320
EqualizeVoltage 252.08 180 320
BoostVoltage 252.08 180 320
Rectifier-MinimumTestVoltage 201.67 180 320
SafeVoltage 235.58 180 320
OverVoltageProtection 265.83 180 320
AbsorptionVoltage 252.08 180 320
AbsorptionArmingVoltage 220 180 320
TempCompMaxVoltage 254.38 N/A 320
TempCompMinVoltage 240.63 180 N/A
BatteryStringNumberofCells 110 1 200
TempCompVoltageWarning 4.58 0 4.58
BatteryTestTerminationVoltage 203.96 180 320
OutputVoltageHighAlarm 254.38 180 320
OutputVoltageVeryHighAlarm 258.96 180 320
OutputVoltageLowAlarm 220 180 320
OutputVoltageVeryLowAlarm 213.13 165 320
0350058-J0 Rev AL Page 277