Cordex®CXCHPControllerSoftwareManual|21-Maintainingmodules
4. Measuretheactualtemperatureattheprobe.
5. Recordthemeasuredvalue:____________or℉.
6. Subtractthedisplayedvalue:____________or℉, fromthewebinterface.
7. Calculatethenewoffset:_____________or℉. CalculationOffset=MeasuredValue-
DisplayedValue
8. SelecttheEDIT buttonoftheOffset field.EnterthenewoffsetindegreesandselectSave.
9. VerifythattheOffset fieldwasupdated,andthatthenewdisplayedvaluematchesthemeasured
value.
21.1.5. Test relays
To test relays:
1. GotoModules andselecttheGO TO buttonofthedevicetobetested.
2. IntheRelays table,selecttheTest Relay buttonoftheselectedrelay.
3. Iftherelayisinandenergizedstateitwillbecomede-energizedforoneminute.Ifitisde-
energized,itwillbeenergizedduringthetest.Toendthetestearly,selecttheStop Test button.
4. Relayscanalsobetestedbygoingtotheindividualrelaymenu.
21.1.6. Test comms lost action
To test the comms lost action feature:
1. GotoModules andselecttheGO TO buttonofthedevicetobetested.
2. IntheRelays table,selecttheGO TO buttonoftherelaytobeconfiguredfortheComms Lost
Action.
3. Ensuretherelay’snormalpositionissettoEnergized.
4. Onceconfigured,gotoController > Communication > CAN anddisableeachenabledCANbus.
5. Waitfiveminutes.
6.
Afterfiveminutestherelayconfiguredasacommslostrelaywillde-energize.Toconfirm,verifythe
relaystateusingadigitalmultimeter.Re-enabletheCANbusesandtherelaywillenergize.
Notice: The Comms Lost Action is only available on controller version 6.10 and later, and
firmware in the CAN module must have a version that supports this feature.
21.1.7. Enable temperature sensor failure alarms
TheTemperature Sensor Failure alarmactivatesifthevoltageonthetemperatureinputisbelowor
abovetheoperatingrangeoftheinput.Ifthesensorisunplugged,thevoltagewillbezeroandthealarm
activates.Ifyouaccidentallyapplybusvoltagetothetemperatureinput,thealarmactivates.
To enable temperature sensor alarms:
Page 230 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish