Cordex®CXCHPControllerSoftwareManual|13-Cordex®CXPS-HSSHyperboostconvertersystem
13.6. Configure the current transducer
Thesystem,bydefaultdoesnotcontainanycurrenttransducers.Youcanaddorremovecurrent
transducersasneeded.ToconfigureacurrenttransduceryouneedavoltageinputonanADIOmodule.
To configure a current transducer:
1. Gotothesystemwhereyouwanttoaddthetransducerandnavigatetotheinventorypage.Goto
Systems > Inventory > Other Transducers > Current Transducer.Therewillbealistofcurrent
transducersinthesystem.Addorremovethemfromthispage.
2. SelecttheGO TO buttonfortheCurrent Transducer youwanttoconfigure.
3. IntheConfiguration tableassigntheCurrent Transducer anameandadescription.
4. SelecttheCT Current Source.Thiscanbeanyvoltagesource.
5. EntertheRange in Amps.
6. EntertheRange in Volts.
7. Optional:entertheOffset calibrationfortheCurrent Transducer ifthereadingerroristoolowor
high.
13.7. Configure the general purpose transducer
Thesystem,bydefaultdoesnotcontainanygeneralpurposetransducers.Youcanaddorremove
generalpurposetransducersasneeded.Toconfigureageneralpurposetransduceryouneedavoltage
inputonanADIOmodule.
To configure a general purpose transducer:
1. Gotothesystemwhereyouwanttoaddthetransducerandnavigatetotheinventorypage.Goto,
Systems > Inventory > Other Transducers > General Purpose Transducer.Therewillbealist
ofgeneralpurposetransducersinthesystem.Addorremovethemfromthispage.
2. SelecttheGO TO buttonfortheGeneral Purpose Transducer youwanttoconfigure.
3. IntheConfiguration tableassignanameandadescription.
4. SelecttheTransducer Input Source.Thiscanbeanyvoltagesourceoracustomdata.
5. EntertheTransducer Input Minimum in Volts andTransducer Input Maximum in Volts.
6. EntertheTransducer Output Minimum andTransducer Output Maximum.
7. SelecttheUnits and Precision
8. Optional:EntertheOffset calibrationforthecalculatedValue ifthereadingerroristooloworhigh.
TheCalculated Slope andtheOffset areusedtoconverttheInput Source Value totheValue.The
valueisdisplayedintheselectedunitsandprecision.
13.8. Matrix C16™ high density connectorized DC distribution breaker
panel
ThissectionprovidesabriefoverviewofthecomponentsandfunctionsofMatrixC16™highdensity
connectorizedDCdistributionbreakerpanel.
0350058-J0 Rev AL Page 143

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish