Cordex®CXCHPControllerSoftwareManual|23-Troubleshooting
5. Ifrequired,thisvaluecanbechanged.Therecommendedvalueis100.Changethevaluedirectly
inthetexteditorandsave.Ensurethatonlythevalueischangedandtheenclosingsemicolonsare
preserved.
6. ReturntothecontrollerinterfaceandselectUpload Configuration File to Controller intheT2S
Expert Operations table.
7. SelecttheT2Sconfigurationfilethatwasjustedited,andthenselectUpload.
8. IntheT2S Expert Operations table,theSend To T2S.Waitforthetransfertocomplete.
23.4. Troubleshooting a line power system
Thissectiondescribestohowtotroubleshootlinepowersystemalarms,overload,andtransientevents.
23.4.1. Resolving line power system alarms
Someofthealarmsfromthelinepowersystemaregeneratedbythelinepowersystemmodules.These
alarmsareInput Voltage High/Low Shutdown,High Temperature Shutdown,Temperature Warning,
Module Connection Error,andanyalarmwithChannel initsname.Thissectiondescribeshowtoidentify
themodulecausingthealarm.
1. Whenoneofthelinepowersystemspreviouslymentionedisactive,gotoSystems > Line Power
System > Layout.
2. OntheLayout pagelookforamoduleoutlinedinred,orachannelwiththeredexclamationmark
iconthatsignifiesachannelalert.Thetableshowsthephysicallocationofthemoduletohelpfind
it,shoulditneedtobereplaced.
3. Selectthechannelwiththealerticon.Ifthemoduleisoutlinedinred,butnochannelsappearsto
beinalert,selectanychannel.
4. Thechanneldetailsdisplayinanothertable.
5. Selectthelinktoshowthemoduledetails.
6. IntheAlerts table,sorttheValue columntoshowalltheactivealertsatthetop.Thisidentifiesall
thealertsthatareactiveonthemodule.Usethehelptextforthealertstodecideonthecorrective
action.
23.4.2. Fan tray alarms
Thelinepowersystemmaybeinstalledwithoneormoreoptionalfantrays.ThefantrayisaCAN
connectedADIOdevicethathasaFan Fail alarmassociatedwithit.Thissectiondescribeshowto
identifythemodulecausingthealarm.
1. GotoAlarms > Active Alarms.
2. Inthe Active Alarms table,findtheFan Fail Alarm andnotethenameofthefantraythatis
responsible.Thisconfirmsthealarmiscausedbythefantrayandnotsomeotherdevice.
3. LookforthephysicalfantraywiththeredLED.Repairorreplaceasrequired.
0350058-J0 Rev AL Page 265

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish