21. Maintaining modules
Whenmaintainingyourmodulesalwayscheckforknownissueswithinthereadmefilethatshipswithyour
software.Thissectionofthemanualcoversthefollowing:
ADIOperipheralconfigurationandmaintenance
Modulefirmwareupgrades
21.1. ADIO peripheral maintenance
TolocateconnectedADIOdevicesgotoModules,intheCAN Modules tablefindthedeviceyouwantto
locateandthenselectLocate button.TheLEDsontheselectedADIOmodulewillflash.
21.1.1. Configure an ADIO peripheral
To configure an ADIO peripheral:
1. ToviewstatusofinputsandoutputsgotoModules andselectanADIO.
2. Toconfigureadigitalinput,selecttheGO TO buttonfortheselecteddigitalinput.Activewhencan
beconfiguredasEnergized orNot Energized.
3. Toconfigurearelay,selecttheGO TO Buttonfortheselectedrelay.Normalpositionofthe
relaycanbesettoEnergized orNot Energized.Arelaycanalsobesettode-energizeif
communicationislostbetweenthecontrollerandtheADIOmodule.Todothis,settheComms
Lost Action toDe-Energize on Comms Lost.Thisfeaturewasaddedincontrollersoftware
version6.10andrequiresup-todatefirmwareontheADIOmodule.Thisfeaturecannotbeused
onrelaysthatareusedforcontrolfunctions,likedisconnects.
4. Tochangethecalibration,selecttheGO TO buttonfortheselectedanaloginput.Youmustbe
loggedinasanAdministratortolaunchtheFactory Calibration wizard.
5. TheComms Lost Timeout shouldnormallyleftatthedefaultvalue.Itisonlyusedinadvanced
configurationswitharedundantcontrollerandADIOmodule.
21.1.2. Replace an ADIO peripheral
ADIOmoduleshavealotofconfigurationandoftenhavemanylinkstothingssuchasthesystemvoltage
oralarmrelays.BecausesomuchconfigurationistiedtoanADIOmodule,thereisacommandfor
replacingtheADIOmodulethatretainsallofitsconfiguration.
To replace an ADIO peripheral:
1. GotoModules.
2.
UsetheLocate buttontofindthetwoADIOmodules,theoldone(tobereplaced)andthenew
one.Itmaybeusefultonotethetwoserialnumbers,intheidentitycolumn,iftherearemultiple
ADIOmodulesinthelist.
TheLocatebuttonwillonlyworkonADIOmodulesthathave“Normal”Communicationstatus.
0350058-J0 Rev AL Page 223

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish