Cordex®CXCHPControllerSoftwareManual|22-Usingcustomviews,data,timers,counters,scheduler,andcustomactions
To remove a table from the custom view:
1. IntheCustom View,makenoteofthenameofthetablefromthedeletedsystem.
2. GotoController > Settings > User Interface.IntheCustom Views tablenavigateintothe
Custom View associatedwiththeissue.
3. IntheComponents table,locatethetablenamefromthedeletedsystem.
4.
IntheActions columnoftheComponentstable,selectRemove.
GoingbacktotheCustom View,thetablewillnolongerbevisible.
22.1.6. Add an existing table to the custom view
Yourcustomviewmayreferenceatablefromasystemthathasbeendeleted.
To re-add an existing table:
1. Re-instatethepreviouslydeletedsystemtothecontroller.
2. GotoController > Settings > User Interface.IntheCustom Views table,navigateintothe
Custom View.
3. SelecttheGO TO button.
4. IntheComponents table,launchtheAdd Existing Table wizardtoaddtherequiredtablethat
wasunlinked/missing.
22.2. Custom data
TheCustom Data featureallowsyoutocreatecomplexexpressionsthatcanbeusedto:
Provideflexiblewaystomonitorandcontrolasystem
Createcustomconditionsforuseralarmsandrelaycontrol
Customdatacanbeusedtocalculatevaluesthatrepresentvoltages,digitalinputs,orcurrentsinthe
system.
Forexample,inasystemthathasmultipleloadshunts,customdatacanbeusedtosumalltheshunt
currents,andthenthecustomdataresultcanbemappedtoasingle-loadinventoryiteminaDCsystem.
Customdatacanalsobeusedastheinputconditionforauseralarmthatallowsforcustomcontrolof
relayoutputsonADIOmodules.
22.2.1. Configure custom data
Customdatahasfourconfigurationfields:
Name
Description
Equation
Numeric Units and Precision
0350058-J0 Rev AL Page 237