Cordex®CXCHPControllerSoftwareManual|14-Generator
pushes.Thissectionalsodescribeswhattodoifthegeneratorstateshowssuspendedbecauseof
aconfigurationerror.
6. SeeAlarms (on page 152) toconfigurethealarmsintheeventofanadverselyfunctioning
system.
7. Oncefullyconfigured,enabletheGenerator Control.InsidetheGenerator Control pageand
intheGenerator Control table,selecttheEDIT buttonofGenerator Control toenablethe
automaticgeneratoron/offcontroltocommandtheGenerator Control Relay
14.4. Start and stop conditions
Theautomaticon/offcontrolofthegeneratorisbasedonstartconditionsandstopconditions.By
customizingthestartandstopconditions,theusercanadjustthegeneratorcontrolfortheirspecific
situation.Forexample,startandstopconditionscanbeaddedwhichrunthegeneratorbasedona
scheduleinordertoexercisethegenerator.
Thestartandstopconditionsaddgreatversatilitytothegeneratorcontrol;however,caremustbetaken
toensuretheuser'scustomizationbehavesasanticipated.Forexample,ifthegeneratorhasrunpast
theconfiguredMinimum Runtime andtheCall to Stop becomestrue,itwillshutdown.ButiftheCall to
Start isalsotrue,thegeneratorwillimmediatelystartupagain.
14.4.1. Default start and stop conditions
WhenageneratoriscreatedonapowersystemwithaDCsystemandbattery,thegeneratorwillbe
setupbydefaulttostartuponlowDCsystemvoltage,andstopwhenthebatteryreturnstofloatmode.
Table 14-1 DefaultstartandstopconditionswhenaDCsystemandbatteryarepresent
Condition name Value to test
DefaultStartCondition StartOnLowVoltage DCSystem:SystemVoltage
DefaultStopCondition StopWhenBatteryCharged Battery:BatteryMode
Ifthereisnobattery,thegeneratorwillbesetupbydefaulttostartuponlowDCSystemvoltage,andstop
whentheitapproachestoSystemFloatVoltage.
Table 14-2 DefaultstartandstopconditionswhenaDCsystemispresentwithoutabattery
Condition name Value to test
DefaultStartCondition StartOnLowVoltage DCSystem:SystemVoltage
DefaultStopCondition StopOnFloatVoltage DCSystem:SystemVoltage
IfthereisnoDCsystem,thennodefaultstartorstopconditionswillbecreated.Toaddcustomstartand
stopconditions,seeAddstartandstopconditions (on page 147).
14.4.2. Add start and stop conditions
0350058-J0 Rev AL Page 147

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish